Communication Protocols
Modbus
®
Values
Value
Description
Default
Size
Menu path
NoOfRequestsTotal
Total number of requests.
Includes requests for
other slaves.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfRequestsForMe
Total Number of requests
for this slave.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfResponse
Total number of requests
having been responded.
Only available if:Device
planning = TCP.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfResponsTimeOverr
uns
Total number of requests
with exceeded response
time. Physically
corrupted Frame.
Only available if:Device
planning = RTU.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfOverrunErros
Total Number of Overrun
Failures. Physically
corrupted Frame.
Only available if:Device
planning = RTU.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfParityErrors
Total number of parity
errors. Physically
corrupted Frame.
Only available if:Device
planning = RTU.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfFrameErrors
Total Number of Frame
Errors. Physically
corrupted Frame.
Only available if:Device
planning = RTU.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfBreaks
Number of detected
communication aborts.
Only available if:Device
planning = RTU.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
NoOfQueryInvalid
Total number of Request
errors. Request could
not be interpreted.
0
0 - 9999999999
[Operation
/Count and RevData
/Modbus]
Page 192
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...