Trip and Breaker Management
Global Protection Parameters of the Breaker Wear Module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the
module, if blocking is
activated (allowed) within
a parameter set and if the
state of the assigned
signal is true.
1..n, Assignment List
-.-
[Protection Para
/Global Prot Para
/CB Manager
/BW]
ExBlo2
External blocking of the
module, if blocking is
activated (allowed) within
a parameter set and if the
state of the assigned
signal is true.
1..n, Assignment List
-.-
[Protection Para
/Global Prot Para
/CB Manager
/BW]
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/Global Prot Para
/CB Manager
/BW]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/Global Prot Para
/CB Manager
/BW]
Operations Alarm
Service Alarm, too many
Operations
1 - 65535
100
[Protection Para
/Global Prot Para
/CB Manager
/BW]
Isum Intr Alarm
Alarm, the Sum (Limit) of
interrupting currents has
been exceeded.
0 - 2500000A
10000A
[Protection Para
/Global Prot Para
/CB Manager
/BW]
EN MRM4 01/11
Page 259
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...