Recorder
The parameter
»Auto Delete«
defines how the device shall react if there is no saving place available. In case
»Auto Delete«
is
»active«
, the first recorded fault will be overwritten according to the FIFO principle. If the
parameter is set to
»inactive«
, recording of the fault events will be stopped until the storage location is released
manually.
Read Out the Fault Recorder
The measured values at the time of tripping are saved (failure safe) within the fault recorder. If there is no more
memory free, the oldest record will be overwritten (FIFO).
In order to read out a failure record:
•
Call up the main menu;
•
Call up the sub-menu Operation/Recorders/Fault rec.;
•
Select a fault record; and
•
analyze the corresponding measured values.
Page 164
EN MRM4 01/11
Start: 1
Trigger
>1
Start: 2
Trigger
Start: 3
Trigger
Start: 4
Trigger
Start: 5
Trigger
Start: 6
Trigger
Start: 7
Trigger
Start: 8
Trigger
Man Trigger
Recording
>1