Supervision
Setting Group Parameters of the CBF
In order to prevent a faulty activation of the BF Module, the pickup (alarm)
time must be greater than the sum of:
•
The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
•
+ The tripping delay of the device (please refer to the Technical Data
section);
•
+ The security margin; and
•
+ The operating time.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or
deactivation of
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/CBF]
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/Supervision
/CBF]
I-CBF >
Current level that needs
to exist after Trip
Command has been
given.
0.00 - 0.10In
0.00In
[Protection Para
/<n>
/Supervision
/CBF]
t-CBF
If the delay time is
expired, an CBF alarm is
given out.
0.00 - 10.00s
0.20s
[Protection Para
/<n>
/Supervision
/CBF]
EN MRM4 01/11
Page 405
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...