Trip and Breaker Management
Name
Description
Assignment via
Ready-I
Module input state: CB ready
[Protection Para
/Global Prot Para
/CB Manager
/CB]
CB Manager Signals (Outputs States)
Name
Description
TripCmd
Signal: Trip Command
Ack TripCmd
Signal: Acknowledge Trip Command
Pos
Signal: Circuit Breaker Position (0 = Indeterminate, 1 = OFF, 2 =
ON, 3 = Disturbed)
Ready
Signal: Circuit breaker is ready for operation.
Manual OFF
Signal: Circuit breaker was switched off manually.
Manual ON
Signal: Circuit breaker was switched on manually
Pos OFF
Signal: Circuit Breaker is in OFF-Position
Pos ON
Signal: Circuit Breaker is in ON-Position
Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Breaker Position.
The Position Indicators contradict themselves. After expiring of a
supervision timer this signal becomes true.
Breaker Wear
Available elements:
BW
Principle – General Use
The sum of the accumulated interrupted currents are monitored by the Breaker Wear Module.
Device Planning Parameters of the Breaker Wear Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
use
[Device planning]
Page 258
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...