Trip and Breaker Management
Breaker Wear Input States
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/CB Manager
/BW]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/CB Manager
/BW]
Breaker Wear Signals (Output States)
Name
Description
active
Signal: active
ExBlo
Signal: External Blocking
Operations Alarm
Signal: Service Alarm, too many Operations
Isum Intr trip: IL1
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL1
Isum Intr trip: IL2
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL2
Isum Intr trip: IL3
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded: IL3
Isum Intr trip
Signal: Maximum permissible Summation of the interrupting
(tripping) currents exceeded in at least one phase.
Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip commands
Res Sum trip
Signal: Reset summation of the tripping currents
Breaker Wear Counter Values
Value
Description
Menu path
TripCmd Cr
Counter: Total number of trips of the
switchgear (circuit breaker, load break
switch…).
[Operation
/History
/TotalCr]
Breaker Wear Values
Value
Description
Default
Size
Menu path
Sum trip IL1
Summation of the tripping
currents phase1.
0A
0 - 65535A
[Operation
/History
/TotalCr]
Page 260
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...