Installation and Connection
OR - 3AI X - Output Relays and System Contact
The number of the binary output relay contacts is related to the type of the device or type code. The binary
output relays are potential-free contacts. In chapter [Assignment/binary outputs] the assignment of the binary
output relays is specified. The changeable signals are listed in the »assignment list« which can be found in the
appendix.
Make sure that the tightening torque is 0.56-0.79 Nm [5-7 In-lb].
Please duly consider the current carrying capacity of the binary output
relays. Please refer to the Technical Data.
The
System-OK contact (SC relay)
cannot be configured. The system contact is a changeover contact that
picks up when the device is free from internal faults. While the device is booting up, the
System OK relay (SC)
remains dropped-off (unenergized). As soon as the system is properly started (and protection is active), the
System Contact picks up and the assigned LED is activated accordingly (please refer to the Self Supervision
chapter).
For details on the Analogue Output please refer to the Technical Data.
Page 36
EN MRM4 01/11