Device Parameters
Name
Description
Assignment via
PS1-I
State of the module input respectively of the
signal, that should activate this Parameter
Setting Group.
[Protection Para
/PSet-Switch]
PS2-I
State of the module input respectively of the
signal, that should activate this Parameter
Setting Group.
[Protection Para
/PSet-Switch]
PS3-I
State of the module input respectively of the
signal, that should activate this Parameter
Setting Group.
[Protection Para
/PSet-Switch]
PS4-I
State of the module input respectively of the
signal, that should activate this Parameter
Setting Group.
[Protection Para
/PSet-Switch]
System Module Signals
Name
Description
Reboot
Signal: Rebooting the device: 1=Restart initiated by power supply;
2=Restart initiated by the user; 3=Set on defaults (Super Reset);
4=Restart by the debugger; 5=Restart because of configuration
change; 6=General failure; 7=Restart initiated by System Abort
(host side); 8=Restart initiated by watchdog timeout (host side);
9=Restart initiated by System Abort (dspside); 10=Restart initiated
by watchdog timeout (dspside); 11=Power supply failure (short
term interruption) or power supply voltage to low; 12=illegal
memory access.
Act Set
Signal: Active Parameter Set
PS 1
Signal: Parameter Set 1
PS 2
Signal: Parameter Set 2
PS 3
Signal: Parameter Set 3
PS 4
Signal: Parameter Set 4
PSS manual
Signal: Manual Switch over of a Parameter Set
PSS via Scada
Signal: Parameter Set Switch via Scada
PSS via Inp fct
Signal: Parameter Set Switch via input function
min 1 param changed
Signal: At least one parameter has been changed
Param to be saved
Number of parameters to be saved. 0 means that all parameter
changes are overtaken.
Ack LED
Signal: LEDs acknowledgement
Ack BO
Signal: Acknowledgement of the Binary Outputs
Ack Counter
Signal: Reset of all Counters
Ack Scada
Signal: Acknowledge Scada
Ack TripCmd
Signal: Reset Trip Command
Ack LED-HMI
Signal: LEDs acknowledgement :HMI
Ack BO-HMI
Signal: Acknowledgement of the Binary Outputs :HMI
Ack Counter-HMI
Signal: Reset of all Counters :HMI
Ack Scada-HMI
Signal: Acknowledge Scada :HMI
Page 232
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...