Protective Elements
Parameter
Description
Setting range
Default
Menu path
ExBlo Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I<
/I<[1]]
Blo TripCmd
Permanent blocking of
the Trip Command of the
module/stage.
inactive,
active
inactive
[Protection Para
/<n>
/I<
/I<[1]]
ExBlo TripCmd Fc
Activate (allow) or
inactivate (disallow)
blocking of the
module/stage. This
parameter is only
effective if a signal is
assigned to the
corresponding global
protection parameter. If
the signal becomes true,
those modules/stages
are blocked that are
parametrized "ExBlo
TripCmd Fc=active".
inactive,
active
inactive
[Protection Para
/<n>
/I<
/I<[1]]
Undercurrent
Underload Pickup based
on a multiplier of Ib.
0.05 - 0.90Ib
0.50Ib
[Protection Para
/<n>
/I<
/I<[1]]
Alarm Mode
Indicates if one, two of
three or all phases are
required for operation.
any one,
all
any one
[Protection Para
/<n>
/I<
/I<[1]]
t
Tripping delay
0.4 - 1200.0s
I<[1]: 2.0s
I<[2]: 10.0s
I<[3]: 0.4s
[Protection Para
/<n>
/I<
/I<[1]]
Page 346
EN MRM4 01/11
Содержание MRM4
Страница 1: ...MRM4 HighPROTEC Motor Protection Device Manual DOK HB MRM4E...
Страница 3: ...Order Code EN MRM4 01 11 Page 3...
Страница 18: ...Important Definitions Page 18 EN MRM4 01 11 41 SG Prot ON 42 SG ON Cmd SG Prot ON SG ON Cmd...
Страница 115: ...Navigation Operation Navigation Operation EN MRM4 01 11 Page 115 1 2 3 5 7 6 8 10 9...
Страница 162: ...Recorder Name Description I 2 TripCmd Signal Trip Command Page 162 EN MRM4 01 11...