background image

 

 

Page 1 of 6

 

T

OTAL

P

AC

2 Integrated Fire Protection System

 

Cycling Wet Pipe Systems

 

 

 

FM-072G-0-143 E 

General 

1.  Applicable Standards 

The 

T

OTAL

P

AC

2

 complies with the following standards: 

NFPA-13 Sprinkler Systems; 

NFPA-15 Water Spray Fixed Systems; 

NFPA-16 Foam-Water Deluge and Foam-Water Spray 
Systems; 

NFPA-72 Fire Alarm Systems. 

Before the installation, the contractor installing the unit shall 
be familiar with the following documents and standards: 

Applicable Local & State Building Codes 

Any additional requirements of the Local Authority 
Having Jurisdiction. 

2.  Listings and Approvals 

In addition to being fabricated under tight ISO-9001 
manufacturing and quality control procedures, your 

T

OTAL

P

AC

2

 Unit has also been tested and approved by 

recognized laboratories.  Here is the list of Listings & 
Approvals it meets: 

Underwriters Laboratories Inc. (UL): Cycling Wet Pipe 
TotalPac2 systems are UL Listed under "Special System 
Water Control Valves - Assembled Units, category 
# VKYL.EX4641". 

Factory Mutual Research <FM>: Cycling Wet Pipe 

T

OTAL

P

AC

2

 systems are FM Approved under the 

heading: "Automatic Water Control Valves" when 
installed with specific components.  

NYC-MEA:  Cycling Wet Pipe 

T

OTAL

P

AC

2

 systems are 

MEA Approved under New-York City's Fire Dept. 
Information Bulletin # 1-92 under section MEA 89-92-E, 
Vol. XXVI. 

Note:

  Although most 

T

OTAL

P

AC

2

 units are Listed, custom 

built units are sometimes supplied on request.  Components 
in these special units maintain their individual 
Listings/Approvals but the units are not Listed as an 
assembled unit. 

CAUTION !  

Any unauthorized modification or addition 

made on-site to a factory built Listed Unit will void this 
Listing.  Such modifications or additions may void the 
unit's warranty as well.  Consult your nearest FireFlex 
Systems Authorized Distributor before proceeding with 
such modifications or additions. 

3.  Environment

 

T

OTAL

P

AC

2

 units shall be installed in a dry and clean 

location.  Verify that all equipment is properly heated and 
protected to prevent freezing and physical damage. 
The unit and it's components must be kept free of foreign 
matter, freezing conditions, corrosive atmospheres, 
contaminated water supplies, and any condition that could 
impair its operation or damage the components. 
The frequency of the inspections and maintenance will vary 
depending on these environmental conditions.  The owner is 

responsible for maintaining the fire protection system and 
devices in proper operating condition.   
Refer to CONFIGURATION DESCRIPTION for 
maintenance instructions. 

4.  General Description 

There are various types of wet pipe systems, all of them 
using closed automatic sprinklers in the sprinkler piping. 
This 

T

OTAL

P

AC

2

 

integrated fire protection system by 

FireFlex Systems Inc

. consists of a cycling wet pipe 

system trim totally pre-assembled, pre-wired and factory 
tested. All electrical and mechanical components of the 
system are contained in one single unit.   
The only connections required for installation are the 
water supply inlet, water discharge outlet, main drain, and 
the electrical detection and alarm connections.  The 
discharge outlet is connected to a fixed piping system of 
automatic sprinklers.  Water is the extinguishing agent.   
Wet pipe systems are usually supervised.  The 

T

OTAL

P

AC

2

 

system is completely supervised in order to 

monitor its integrity.  The sprinkler piping is supervised by 
the water.  If there is a leak on the system or if a sprinkler 
head is accidentally broken, an audible signal will sound.   
Electrical detectors and associated wiring are also 
supervised. 
The most common applications are any structure not 
subject to freezing, to automatically protect the structure, 
contents and/or personnel from loss due to fire.  The 
structure must be substantial enough to support the 
piping system filled with water. 

Using water as the extinguishing agent, one wet pipe 
system can cover as much as 52,000 square feet in a 
single fire area.  Small unheated areas of a building may 
be protected by a wet system if an antifreeze-loop or 
auxiliary dry system is installed.  For rules and limitations, 
see appropriate codes and standards. 

Systems should be designed by qualified fire-protection 
engineers in conjunction with the appropriate Authority 
Having Jurisdiction. 

Note:  

Each 

T

OTAL

P

AC

2

 Unit is identified with it's unique 

Serial Number.  This number is located on a sticker 
inside the main door panel and is used to maintain a 
record in our computerized data base.  Have this Serial 
Number handy when calling for information on your unit 
(format is TOT#####). 

5.  Features

 

The 

T

OTAL

P

AC

2

 unit is superior than many other products 

available on the market now and has been manufactured by 
the company that has introduced and developed the concept 
of integrated fire protection systems in the market. 
Main features are: 

Trouble free design for safe and easy application 

Cycling trim available in 5 sizes from 1½" to 6" diameter 

Uses the Viking Flow Control Valves 

Integrated Control Panel 

Содержание TOTALPAC2

Страница 1: ...intaining the fire protection system and devices in proper operating condition Refer to CONFIGURATION DESCRIPTION for maintenance instructions 4 General Description There are various types of wet pipe systems all of them using closed automatic sprinklers in the sprinkler piping This TOTALPAC2 integrated fire protection system by FireFlex Systems Inc consists of a cycling wet pipe system trim total...

Страница 2: ...s been satisfied Should the fire rekindle the Firecycle III will initiate the sequence again This unique cycling feature will repeat as long as power is available to the panel helping to minimize water usage water damage and the danger of pollution to surrounding areas Firecycle III systems are also Fail Safe Note TOTALPAC2 Firecycle III Systems are available with electrical type release and the i...

Страница 3: ...ivates latching normally open solenoid valve F1 closed Water discharges until all Firecycle Detectors have reset cooled below their set point After all detectors have reset the control panel activates the Soak Timer allowing the system to continue discharging water for a preset time period When the Soaking Timer has expired the control panel de energizes normally closed Release Solenoid Valve F2 a...

Страница 4: ...larms it is important to remove trapped air from the system when filling it with water Air trapped in the system may also cause intermittent operation of the water motor gong during a sustained flow of water such as the flow required by an open sprinkler or the system test valve Consider installation of auxiliary vents to facilitate venting CAUTION Opening of the water supply main control valve A2...

Страница 5: ...on Main Drain Test Riser Flow Test to determine if change in water supply or control valve position Test procedure Record the pressure indicated by the supply water gauge Fully open the main drain valve Record residual pressure Close the main drain valve slowly Record the time taken for supply water pressure to return to the original pressure Open the alarm control valve Semi Annually Valve superv...

Страница 6: ...Page 6 of 6 TOTALPAC2 Integrated Fire Protection System Cycling Wet Pipe Systems FM 072G 0 143 E ...

Отзывы: