Page 1 of 6
T
OTAL
P
AC
2 Integrated Fire Protection System
Cycling Wet Pipe Systems
FM-072G-0-143 E
General
1. Applicable Standards
The
T
OTAL
P
AC
2
complies with the following standards:
-
NFPA-13 Sprinkler Systems;
-
NFPA-15 Water Spray Fixed Systems;
-
NFPA-16 Foam-Water Deluge and Foam-Water Spray
Systems;
-
NFPA-72 Fire Alarm Systems.
Before the installation, the contractor installing the unit shall
be familiar with the following documents and standards:
-
Applicable Local & State Building Codes
-
Any additional requirements of the Local Authority
Having Jurisdiction.
2. Listings and Approvals
In addition to being fabricated under tight ISO-9001
manufacturing and quality control procedures, your
T
OTAL
P
AC
2
Unit has also been tested and approved by
recognized laboratories. Here is the list of Listings &
Approvals it meets:
-
Underwriters Laboratories Inc. (UL): Cycling Wet Pipe
TotalPac2 systems are UL Listed under "Special System
Water Control Valves - Assembled Units, category
# VKYL.EX4641".
-
Factory Mutual Research <FM>: Cycling Wet Pipe
T
OTAL
P
AC
2
systems are FM Approved under the
heading: "Automatic Water Control Valves" when
installed with specific components.
-
NYC-MEA: Cycling Wet Pipe
T
OTAL
P
AC
2
systems are
MEA Approved under New-York City's Fire Dept.
Information Bulletin # 1-92 under section MEA 89-92-E,
Vol. XXVI.
Note:
Although most
T
OTAL
P
AC
2
units are Listed, custom
built units are sometimes supplied on request. Components
in these special units maintain their individual
Listings/Approvals but the units are not Listed as an
assembled unit.
CAUTION !
Any unauthorized modification or addition
made on-site to a factory built Listed Unit will void this
Listing. Such modifications or additions may void the
unit's warranty as well. Consult your nearest FireFlex
Systems Authorized Distributor before proceeding with
such modifications or additions.
3. Environment
T
OTAL
P
AC
2
units shall be installed in a dry and clean
location. Verify that all equipment is properly heated and
protected to prevent freezing and physical damage.
The unit and it's components must be kept free of foreign
matter, freezing conditions, corrosive atmospheres,
contaminated water supplies, and any condition that could
impair its operation or damage the components.
The frequency of the inspections and maintenance will vary
depending on these environmental conditions. The owner is
responsible for maintaining the fire protection system and
devices in proper operating condition.
Refer to CONFIGURATION DESCRIPTION for
maintenance instructions.
4. General Description
There are various types of wet pipe systems, all of them
using closed automatic sprinklers in the sprinkler piping.
This
T
OTAL
P
AC
2
integrated fire protection system by
FireFlex Systems Inc
. consists of a cycling wet pipe
system trim totally pre-assembled, pre-wired and factory
tested. All electrical and mechanical components of the
system are contained in one single unit.
The only connections required for installation are the
water supply inlet, water discharge outlet, main drain, and
the electrical detection and alarm connections. The
discharge outlet is connected to a fixed piping system of
automatic sprinklers. Water is the extinguishing agent.
Wet pipe systems are usually supervised. The
T
OTAL
P
AC
2
system is completely supervised in order to
monitor its integrity. The sprinkler piping is supervised by
the water. If there is a leak on the system or if a sprinkler
head is accidentally broken, an audible signal will sound.
Electrical detectors and associated wiring are also
supervised.
The most common applications are any structure not
subject to freezing, to automatically protect the structure,
contents and/or personnel from loss due to fire. The
structure must be substantial enough to support the
piping system filled with water.
Using water as the extinguishing agent, one wet pipe
system can cover as much as 52,000 square feet in a
single fire area. Small unheated areas of a building may
be protected by a wet system if an antifreeze-loop or
auxiliary dry system is installed. For rules and limitations,
see appropriate codes and standards.
Systems should be designed by qualified fire-protection
engineers in conjunction with the appropriate Authority
Having Jurisdiction.
Note:
Each
T
OTAL
P
AC
2
Unit is identified with it's unique
Serial Number. This number is located on a sticker
inside the main door panel and is used to maintain a
record in our computerized data base. Have this Serial
Number handy when calling for information on your unit
(format is TOT#####).
5. Features
The
T
OTAL
P
AC
2
unit is superior than many other products
available on the market now and has been manufactured by
the company that has introduced and developed the concept
of integrated fire protection systems in the market.
Main features are:
-
Trouble free design for safe and easy application
-
Cycling trim available in 5 sizes from 1½" to 6" diameter
-
Uses the Viking Flow Control Valves
-
Integrated Control Panel