FIRE FLEX TOTALPAC2 Скачать руководство пользователя страница 3

 

 

Page 3 of 6

 

T

OTAL

P

AC

2 Integrated Fire Protection System

 

Cycling Wet Pipe Systems

 

 

 

FM-072G-0-143 E 

valve).  Consider installation of auxiliary vents to facilitate 
venting. 

 
Placing the system in service 

(Refer to mechanical trim description and TRIM 
SCHEMATIC) 

All initiating devices (detectors), indicating appliances and 
releasing devices must be compatible and approved for use  
with the Firecycle

 III System.  Refer to CONTROLS 

SECTION for the list of compatible devices.  

1.  Verify that the system has been properly tested.  

Emergency Release Valve 

(B10)

 should be OPEN. 

2.  SLOWLY OPEN and secure the system Main Water 

Supply Control Valve 

(D1)

.  Consider venting any 

trapped air in the system. 

3.  CLOSE the Emergency Release Valve 

(B10)

4.  Verify that the Alarm Test Valve 

(B5)

 is CLOSED and 

that all other valves are in their "normal" operating 
position (Refer to TRIM SCHEMATIC for details). 

5. Open 

Firecycle

 III control Panel and press "RESET".  

Release solenoid valve 

(F1)

 should open. 

6.  On new installations, systems that have been placed 

out of service, or where new equipment has been 
installed, trip test system to verify that all equipment 
functions properly.  Refer to MAINTENANCE – 
ANNUALLY for instructions. 

7.  After completing the trip test, perform MAINTENANCE 

– SEMI-ANNUALLY. 

Note:  

When a valve has been removed from service and is 

subject to freezing or will be out of service for an extended 
period of time, all water must be removed from the priming 
chamber, trim piping, water supply piping and any other 
trapped areas. 

Mechanical Trim Section 

1. System Operation

  

In the SET condition: 

System water supply pressure enters the priming chamber 
of the Flow Control Valve 

(A2)

 through the ¼" (8mm) 

priming line which includes a strainer 

(B2)

, a restricted 

orifice 

(B3)

 and a spring check valve 

(B4)

.  Normally open 

solenoid valve 

(F1)

 allows priming water to escape so that 

the Flow Control Valve 

(A2)

 will not set, but remain open, 

filling the system with water. 

In a fire condition:

 

In a fire condition, when the detection system operates, 
system Control Panel activates an alarm and energizes 
normally closed Solenoid valve 

(F2)

 open and normally 

open Solenoid valve 

(F1)

 closed. 

Pressure is released from the priming chamber to open 
drain manifold faster than it is supplied through the 
restricted orifice 

(B3)

.  The Flow Control Valve 

(A2) 

clapper 

remains fully open to allow water to flow into the system 

piping and activate alarm devices, including a water flow 
Alarm Pressure Switch 

(C1)

.  

Water will immediately flow from any sprinklers which may 
have operated.  Water Flow Alarm Switch 

(C1)

 activates, 

latching normally open solenoid valve 

(F1) 

closed.  Water 

discharges until all Firecycle Detectors have reset (cooled 
below their set point).  After all detectors have reset, the 
control panel activates the "Soak Timer" allowing the 
system to continue discharging water for a preset time 
period.   
When the Soaking Timer has expired, the control panel de-
energizes normally closed Release Solenoid Valve 

(F2)

allowing it to close.  (The normally open Release Solenoid 
Valve 

(F1)

 remains energized closed until the control panel 

is manually reset, or both the AC power and battery 
backup have failed). 
The Flow Control Valve 

(A2)

 re-primes and closes, 

stopping the flow of water through the system piping. 
Should a Firecycle

 detector go into alarm at this time, the 

control panel re-energizes normally closed release 
Solenoid valve 

(F2)

 open, and the entire cycle repeats. 

Trouble conditions:

 

- False alarms – If water pressure surges produce false 
alarms check if air is trapped in the sprinkler piping.  
Trapped air can cause false alarms, the alarms to cycle on 
and off during testing and other nuisance problems.  To 
correct bleed as much air as possible from the trapped 
high points of system piping.  This condition can be 
minimized by opening the remote inspectors test valve and 
slowly filling the system with water when placing the 
system in service. 

If the detection system is damaged or malfunctions, the 
Firecycle

 III Control panel will go into alarm and the flow 

control valve will open.  Water will not flow from any 
sprinklers until a sprinkler has operated, as in a fire.  The 
cycling function of the Firecycle III

®

 will not operate in this 

condition and the system must be manually shutoff.  All 
alarms will operate normally.   

If the piping system is damaged sufficiently to activate the 
Water Flow Alarm Switch 

(C1)

, the control Panel will 

energize normally open Release Solenoid Valve

 (F1)

 

closed.  Because a detector has not gone into alarm mode, 
release Solenoid Valve 

(F2)

 will remain non-energized 

closed.  The Flow Control valve 

(A2)

 will re-prime and 

close after a short delay.  This feature ensures that should 
a sprinkler or the system piping become damaged, the 
amount of water which will discharge is limited by the 
system pressure and the location of the system damage. 
Should a Firecycle

 detector detect a fire during this 

condition, normally closed Release Solenoid valve 

(F2)

 will 

be energized open, allowing the Flow Control valve 

(A2)

 to 

open, and water will be discharged from any sprinklers 
which may have operated as a result of the fire, as well as 
from the damaged portion of the system and all alarms will 
operate normally in this condition.

 

If the AC power fails, the Firecycle

 III System continues 

to operate on the standby batteries.  Should both AC and 

Содержание TOTALPAC2

Страница 1: ...intaining the fire protection system and devices in proper operating condition Refer to CONFIGURATION DESCRIPTION for maintenance instructions 4 General Description There are various types of wet pipe systems all of them using closed automatic sprinklers in the sprinkler piping This TOTALPAC2 integrated fire protection system by FireFlex Systems Inc consists of a cycling wet pipe system trim total...

Страница 2: ...s been satisfied Should the fire rekindle the Firecycle III will initiate the sequence again This unique cycling feature will repeat as long as power is available to the panel helping to minimize water usage water damage and the danger of pollution to surrounding areas Firecycle III systems are also Fail Safe Note TOTALPAC2 Firecycle III Systems are available with electrical type release and the i...

Страница 3: ...ivates latching normally open solenoid valve F1 closed Water discharges until all Firecycle Detectors have reset cooled below their set point After all detectors have reset the control panel activates the Soak Timer allowing the system to continue discharging water for a preset time period When the Soaking Timer has expired the control panel de energizes normally closed Release Solenoid Valve F2 a...

Страница 4: ...larms it is important to remove trapped air from the system when filling it with water Air trapped in the system may also cause intermittent operation of the water motor gong during a sustained flow of water such as the flow required by an open sprinkler or the system test valve Consider installation of auxiliary vents to facilitate venting CAUTION Opening of the water supply main control valve A2...

Страница 5: ...on Main Drain Test Riser Flow Test to determine if change in water supply or control valve position Test procedure Record the pressure indicated by the supply water gauge Fully open the main drain valve Record residual pressure Close the main drain valve slowly Record the time taken for supply water pressure to return to the original pressure Open the alarm control valve Semi Annually Valve superv...

Страница 6: ...Page 6 of 6 TOTALPAC2 Integrated Fire Protection System Cycling Wet Pipe Systems FM 072G 0 143 E ...

Отзывы: