FIRE FLEX TOTALPAC2 Скачать руководство пользователя страница 5

 

 

Page 5 of 6

 

T

OTAL

P

AC

2 Integrated Fire Protection System

 

Cycling Wet Pipe Systems

 

 

 

FM-072G-0-143 E 

The comparison determines deterioration of system 
performance or condition and the need for further testing or 
maintenance. 

Monthly: 

.1  Inspection of gauges (water supply and system 

pressure) to ensure good condition and normal water 
supply pressure. 

.2  Flow Control valve shall be externally inspected.  The 

valve inspection shall verify the following: 

a. The gauges indicate normal supply water pressure is 

being maintained. 

b. The valve is free of physical damage. 
c. All valves are in the appropriate open or closed position. 
d. There is no leakage from the alarm drains. 

Quarterly: 

-  Alarm Device (pressure or flow switch). 

(

Testing by opening the inspector's test connection

-  Main Drain Test (Riser Flow Test) to determine if change 

in water supply or control valve position. 

Test procedure: 

Record the pressure indicated by the supply water 
gauge. 

Fully open the main drain valve. 

Record residual pressure. 

Close the main drain valve slowly. 

Record the time taken for supply water pressure to 
return to the original pressure. 

Open the alarm control valve 

Semi-Annually: 

-  Valve supervisory switch shall be tested to verify the 

operation of the switch upon movement of the hand 
wheel. 

Annually: 

Manual Pull station test. 

Record indicating the date of the last trip, tripping time 
and name of organization conducting the test shall be 
maintained at a location available for review by the 
Authority Having Jurisdiction. 

Every 5 years: 

-  Alarm valve and associated strainers, restriction orifice, 

gaskets, moving parts shall be inspected internally. 

-  Test on gauge (gauge precision required: less than 3% 

of the full scale) 

-  Test on control valves operation 

 

Содержание TOTALPAC2

Страница 1: ...intaining the fire protection system and devices in proper operating condition Refer to CONFIGURATION DESCRIPTION for maintenance instructions 4 General Description There are various types of wet pipe systems all of them using closed automatic sprinklers in the sprinkler piping This TOTALPAC2 integrated fire protection system by FireFlex Systems Inc consists of a cycling wet pipe system trim total...

Страница 2: ...s been satisfied Should the fire rekindle the Firecycle III will initiate the sequence again This unique cycling feature will repeat as long as power is available to the panel helping to minimize water usage water damage and the danger of pollution to surrounding areas Firecycle III systems are also Fail Safe Note TOTALPAC2 Firecycle III Systems are available with electrical type release and the i...

Страница 3: ...ivates latching normally open solenoid valve F1 closed Water discharges until all Firecycle Detectors have reset cooled below their set point After all detectors have reset the control panel activates the Soak Timer allowing the system to continue discharging water for a preset time period When the Soaking Timer has expired the control panel de energizes normally closed Release Solenoid Valve F2 a...

Страница 4: ...larms it is important to remove trapped air from the system when filling it with water Air trapped in the system may also cause intermittent operation of the water motor gong during a sustained flow of water such as the flow required by an open sprinkler or the system test valve Consider installation of auxiliary vents to facilitate venting CAUTION Opening of the water supply main control valve A2...

Страница 5: ...on Main Drain Test Riser Flow Test to determine if change in water supply or control valve position Test procedure Record the pressure indicated by the supply water gauge Fully open the main drain valve Record residual pressure Close the main drain valve slowly Record the time taken for supply water pressure to return to the original pressure Open the alarm control valve Semi Annually Valve superv...

Страница 6: ...Page 6 of 6 TOTALPAC2 Integrated Fire Protection System Cycling Wet Pipe Systems FM 072G 0 143 E ...

Отзывы: