2301E Digital Control
Manual 26641
82
Woodward
03 OVERSPEED
(monitor)
When TRUE indicates an engine overspeed.
04 MPU FAIL
(monitor)
When TRUE indicates an MPU failure.
05 ANALOG INPUT #1 FAIL
(monitor)
When TRUE indicates a signal input failure.
06 ANALOG INPUT #2 FAIL
(monitor)
When TRUE indicates a signal input failure.
07 TEST MODE
(monitor)
When TRUE indicates that the Test Mode is active.
08 EXTERNAL SHUTDOWN
(monitor)
Indicates that an external shutdown is active (one of the digital inputs is
configured for an external shutdown).
09 AI CONFIGURATION ERROR
(monitor)
When TRUE, indicates that both analog inputs are configured for the same
function.
10 HIGH PEAK SPEED VALUE
(monitor)
This value is a value of the how high the received engine speed input got to. It
could be used for overspeed detection. It will store the highest value speed of the
engine until the unit is powered down or the 12 RESET HIGH SPEED PEAK
VALUE is reset.
11 LOW PEAK SPEED VALUE
(monitor)
This value is a value of the how low the received engine speed input got to. It will
store the lowest value speed of the engine until the unit is powered down or the
11 RESET HIGH SPEED PEAK VALUE is reset.
12 RESET SPEED PEAK VALUES
dflt = FALSE (FALSE, TRUE)
This value will reset the PEAK SPEED VALUES.
13 MANUAL STOP DATALOG
dflt = FALSE (FALSE, TRUE)
This value will stop the datalog from actively storing data. You can now set up a
computer to download the datalog using the 15 PRINT OUT DATALOG.
14 MANUAL START DATALOG
dflt = FALSE (FALSE, TRUE)
This value will reset re-start the datalog after it has been manually stopped.
15 PRINT OUT DATALOG
dflt = FALSE (FALSE, TRUE)
This value will print out a Datalog on the RS-422 serial port. The Control
Assistant software is used to collect this data. See Appendix E for a description
on how to perform this function.
16 RESET SHUTDOWNS
dflt = FALSE (FALSE, TRUE)
This switch resets the shutdown status.
The engine speed has to be zero before the reset can function.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...