Manual 26641
2301E Digital Control
Woodward
115
10 PORT 1 PARITY IS SET FOR:
(monitor)
Shows the parity setting.
11 PORT 2 SELECT (MODBUS OR DATALOG)
dflt = 1 (1
–2)
Sets weather Port 2 is selected for Modbus output or Datalog output.
12 PORT 2 IS SELECTED FOR:
dflt = 1 (1
–2)
Displays Port 2 selection. Modbus output or Datalog.
13 PORT 2 FAIL
(monitor)
Indicates a hardware fault of the serial RS-422 communication port.
14 PORT 2 BAUD RATE
dflt = 12 (8
–12)
Sets the Baud rate, which defines the transfer rate for port communications:
8 = 9600
9 = 19200
10 = 38400
11 = 57600
12 = 115200
15 PORT 2 BAUD RATE IS SET FOR:
(monitor)
Shows the selected Baud rate.
16 PORT 2 DATA BITS
dflt = 2 (1
–2)
Sets the Data bits input defines the protocol for the number of data bits in the
data packets:
1= 7
2= 8
17 PORT 2 DATA BITS ARE SET FOR:
(monitor)
Shows the selected data bits.
18 PORT 2 STOP BITS
dflt = 1 (1
–3)
Sets the Stop bits, which defines the number of stop bits for the communications
protocol. Stop bits specify the time that elapses between transmitted characters.
1= 1 stop bit
2= 2 stop bits
3= 1.5 stop bits
19 PORT 2 STOP BITS ARE SET FOR:
(monitor)
Shows the selected stop bits setting.
20 PORT 2 PARITY
dflt = 1 (1
–3)
Sets the Parity input defines protocol for the parity. If you selected 8 data bits
select '1' for none:
1= OFF (none)
2= ODD
3= EVEN
21 PORT 2 PARITY IS SET FOR:
(monitor)
Shows the parity setting.
22 PORT 2 TIME OUT (SEC)
dflt = 2.000 (0.00
–100.00)
Sets the Time-out Number of Seconds input defines the Modbus link dead time
allowed before a link error occurs.
23 PORT 2 ADDRESS
dflt = 1 (1
–247)
Sets the Network Address input defines the slave block address on the Modbus
network. The network address may depend on master device allowable
addresses.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...