2301E Digital Control
Manual 26641
132
Woodward
Troubleshooting Charts
Symptom
Cause
Solution
Prime mover will not
start. Actuator not
moving to start fuel
position.
If the actuator moves to
start position, a
problem with the prime
mover fuel supply is
indicated.
Supply voltage polarity reversed
(dc only), or no supply voltage.
On power up the CPU status LED should
come on for 1.5 seconds.
Check for proper voltage from terminals
48(+) to 49(
–). Reverse leads if polarity is
incorrect.
Actuator not responding to input
signal from control.
The hydraulic actuator must
have oil pressure and gear
rotation to operate (respond).
If there is a voltage output at control
terminals 13(+) and 14(
–), but the actuator
does not move, the wiring to the actuator
should be checked for opens or shorts. With
the EG-3P actuator, remember that
terminals C and D of the mating plug should
be jumpered.
Make resistance checks at the actuator.
Coil resistance on Woodward actuators is
approximately 35 ohms. (Read with leads at
terminals 13 and 14 disconnected.)
Start fuel limit set too low.
Check Fuel Demand % in the Display
Menu. If it is not going to Start Fuel value
when cranking, check to see Engine Speed
is reading cranking speed. If Fuel Demand
is reading 0, increase the Start Fuel Limit.
Actuator or linkage.
Check actuator and linkage for proper
installation and operation. Problems may be
oil supply, direction of rotation, insufficient
drainage, linkage, worn actuator
components, or improper adjustment.
No actuator voltage at terminals
13 and 14.
Check for shorted or grounded actuator
leads by removing wires to terminals 13 and
14. Stop prime mover.
Check that Display Menu is reading engine
speed during cranking. If no speed reading,
check the MPU.
Check for at least 1 Vrms at terminals 25
and 26, and at least 5% of the minimum
rated speed frequency range.
Check to make sure that the status LED is
green. If it is red, would mean that the unit
is still in the configure mode. Reset the
control using the “RESET” icon in the
interface software or cycle power to the
control to re-boot.
Speed setting too low on initial
start.
Control may be configured for the wrong
speed range. Check that the number of
teeth and the rated speed have been
entered correctly. Speed setting may be
lower than cranking speed. Control should
be set for rated speed.
LOW IDLE SPEED setting may be
set too low.
Check that the LOW IDLE SPEED setting is
entered correctly.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...