2301E Digital Control
Manual 26641
102
Woodward
02 PRESSURE X1
dflt = 6.000 (
–1000.00–1000.00)
This sets the pressure at the first breakpoint. The limit on fuel demand below this
point is extrapolated from this point and the pressure X2
below.
03 MAP LIMIT Y1
dflt = 100.000 (0.00
–100.00)
This sets the maximum fuel demand at the first pressure setpoint.
04 PRESSURE X2
dflt = 8.000 (
–1000.00–1000.00)
This sets the pressure at the second breakpoint.
05 MAP LIMIT Y2
dflt = 100.000 (0.00
–100.00)
This sets the maximum fuel demand at the second pressure setpoint.
06 PRESSURE X3
dflt = 10.000 (
–1000.00–1000.00)
This sets the pressure at the third breakpoint.
07 MAP LIMIT Y3
dflt = 100.000 (0.00
–100.00)
This sets the maximum fuel demand at the third pressure setpoint.
08 PRESSURE X4
dflt = 15.000 (
–1000.00–1000.00)
This sets the pressure at the fourth breakpoint.
09 MAP LIMIT Y4
dflt = 100.000 (0.00
–100.00)
This sets the maximum fuel demand at the fourth pressure setpoint.
10 PRESSURE X5
dflt = 20.000 (
–1000.00–1000.00)
This sets the pressure at the maximum breakpoint.
11 MAP LIMIT Y5
dflt = 100.000 (0.00
–100.00)
This sets the maximum fuel demand at the maximum pressure setpoint.
12 MAP NEAR FUEL LIMIT %
dflt = 5.000 (0.00
–10.00)
When the maximum air pressure limit comes within the range of this setting the
overload contact is initiated.
13 MAP DELAY TIME CONTACT
dflt = 0.500 ( 0.00
–30.00)
When the maximum air pressure limit is within the near fuel limit range for longer
than this delay time an overload contact is activated.
14 MAP OVERLOAD PULS TIME
dflt = 0.500 (0.00
–100.00)
This is the time for the overload contact to be active. In Configure Menu
D**Discrete Out Options** a discrete output can be setup at parameter 8
(Overload Contact).
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...