2301E Digital Control
Manual 26641
56
Woodward
Send Tunable List is selected to send the tunables from the currently
active tunable view window to the Control. The tunables are sent using the
device selected in the Communications dialog. The Communications dialog will
automatically appear if the preferred transfer protocol, OPC, is not selected.
To send a tunable list to a control, the control must be in IO Lock.
Follow these steps to save and reload the variables from the control:
Step 14:
Control Assistant must be opened to upload or save the variables to your
computer. Click on the “Receive Debug Tunable List” icon
.
Once the list is downloaded, it will ask you to save the file.
Step 15:
The software will ask you where to save the application settings file. The file
extension is .tc
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...