2301E Digital Control
Manual 26641
46
Woodward
Chapter 4.
Entering Control Set Points
Introduction
This chapter contains information on control calibration. This can be done with
either the
Control Assistant
software or the
2301E Toolkit Service Tool
software. Because of the variety of installations, plus system and component
tolerances, the 2301E control must be tuned and configured for each system to
obtain optimum performance.
This chapter contains information on how to enter control set points through the
control's menu system using the Control Assistant and the 2301E Toolkit Service
Tool software. See
Chapter 5, Initial Control Settings
, and
Chapter 6,
Alternate Dynamic Adjustments
, for prestart-up and start-up settings and
adjustments.
An improperly calibrated control could cause an overspeed or other
damage to the prime mover. To prevent possible serious injury from
an overspeeding prime mover, read this entire procedure before
starting the prime mover.
Control Assistant PC Interface
The connection of a computer is only required for calibration and setup of the
2301E control on a prime mover. The computer and Control Assistant or 2301E
Toolkit Service Tool software is not required, and not necessary, for normal
operation of the prime mover, unless Modbus is being used for monitoring.
Control Assistant is similar to the Servlink / Watch Window used on the 2301D. It
provides a means of shutting down and placing the control in the I/O Lock mode
for Configuration, saving values in the control EEPROM, and resetting the
control. Application tunable values can be uploaded, downloaded, and saved to a
file.
A “WinPanel” provides a window for real-time monitoring and editing of all control
Configure and Service Menu parameters and values. Tunable values can be
adjusted in the WinPanel window. Control Assistant communicates with the
control through an RS-232 cable
“null-modem” connection to the communication
port which is configured as a point-to-point only SOS Servlink OPC Server.
Control Assistant Features
Control Assistant is a utility designed to communicate with Woodward controls
over serial or Ethernet connections.
The following features are supported:
Live parameter monitoring and tuning
Tunable maintenance (tunable captures, editing, comparing and transferring
files)
Alarms and Events viewing from SOS servers/controls with AE support
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...