Manual 26641
2301E Digital Control
Woodward
91
I**Dynamics #2**
The Dynamics 2 control parameters are adjusted the same as Dynamics 1
described above. To enable the use of two sets of dynamics, it is necessary to
set Enable 2nd DYNAMICS w/CB below to TRUE. These parameters are in
control only when the CB Aux contact input is closed or if a discrete input is
configured for Select 2
nd
Dynamics and this input is closed.
I**Dynamics #2** parameters 04 thru 10 have the same effect on
speed control response as H**Dynamics #1** parameters 01 thru 07
described above.
01 ENABLE DYNAMICS 2 W/CB
dflt = FALSE (FALSE, TRUE)
02 DELAY DYN 2 ENABLE (SEC)
dflt = 0.00 (0.00
–20.00)
This is the delay time before dynamics #2 are used by the speed control when
the "CB Aux Droop contact" or "Select 2nd Dynamics" input is activated.
03 DELAY DYN 1 ENABLE (SEC)
dflt = 0.00 (0.00
–20.00)
This is the delay time before Dynamics #1 are used by the speed control after the
"CB Aux Droop contact" or "Select 2nd Dynamics" input is de-activated.
04 PROP GAIN 2
dflt = 2.00 (0.001
–100.00)
05 RESET 2
dflt = 1.00 (0.01
–100.00)
06 ACTUATOR COMPENSATION 2
dflt = 0.10 (0.01
–100.00)
07 WINDOW WIDTH 2 (RPM)
dflt = 60.00 (1.00
–200.00)
08 GAIN RATIO 2
dflt = 1.00 (1.00
–10.00)
09 GAIN SLOPE 2
dflt = 0.00 (-50.00
–50.00)
10 GAIN BREAKPOINT 2
dflt = 20.0 (0.00
–100.00)
11 SPEED FILTER FREQ 2 (HZ)
dflt = 12.00 (4.00
–20.00)
12 BUMP ACT TRIG (T THEN F)
dflt = FALSE (FALSE, TRUE)
13 PID DYNAMICS IN USE
(monitor)
This value will indicate which set of dynamics are in use by the controller. The
choices that are shown here are:
PID USING DYNAMICS 1
PID USING DYNAMICS 2
PID USING 5-SLOPE - DYNAMICS 1
PID USING 5-SLOPE - DYNAMICS 2
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...