Manual 26641
2301E Digital Control
Woodward
161
Appendix D.
Software Revision
This is a list of the software changes and enhancements that could affect your
control on the event that the application software is changed in your control. The
software revision of your control can be checked by connecting to the control,
starting the Control Assistant or 2301E Toolkit software and opening Service
Menu “Y”.
Application Software - 5418-6350 New
—Released 30 September 2012
New control
Application Software - 5418-6350 A
—Released 19 February 2013
Software Modifications:
1.
Added logic in the discrete input logic so that if a discreet input were
configured for 50/60 Hertz, that by changing the input, would not affect the
engine speed.
2.
Added logic so that if an analog input were selected for ±3 Vdc input for
synchronizing, a fault latch would not be set if it reached the limits.
3.
Added logic so that an analog input could be used for remote speed control
when in the Modbus Control mode.
4.
Changed logic so that the Port 2 exception errors are reading the right
value.
5.
Added variable in menu Z**COMM PORT SETUP** -
“28 ENABLE ANALOG
INPUT W/MODBUS”. This variable supports the logic change listed in #3
above.
6.
Added two Modbus Boolean write statements to Enable and Disable the
Modbus Control.
7.
Changed the analog input type from 0-5 Vdc to 1-5 Vdc to better match
industry standards.
Application Software - 5418-6350 B
—Released 30 June 2013
Software Modifications:
Fixed an issue where the soft loading feature was working incorrectly. The issue
was that if the Load Contact Input and the CB Aux. Contact Input were closed
simultaneously, the load would immediately jump to the load share level. The soft
load ramp was ignored. If the Load Contact were closed shortly after the CB Aux.
contact, the feature worked properly. The software was changed to correct this
issue. The soft load feature now works if the Load Contact is closed before the
CB Aux. Contact.
Application Software - 5418-6350 C
—Released 29 July 2013
Software Modifications:
1.0 Actuator Compensation #1 and Actuator Compensation #2 adjustments
were swapped. In order to adjust Actuator Compensation #1, Actuator
Compensation #2 had to be adjusted in the second dynamics menu. In order to
adjust Actuator Compensation #2, Actuator Compensation #1 had to be adjusted
in the first dynamics menu. Service Bulletin 01586 was released to explain the
issue. No other changes were made.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...