SERVICE MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MIN.
MAX.
N**LOAD SETTINGS**
01 LOAD DROOP PERCENT
5.000
0.00
12.00
02 LOAD LEVEL VOLTAGE
6.000
0.10
9.00
03 LOAD SHARE GAIN
1.000
0.01
10.00
04 ENABLE ACT POS DROOP
FALSE
TRUE
FALSE
05 ACT POSITION DROOP %
0.000
0.00
100.00
06 ACT OUT AT RATED NO LOAD
20.000
0.00
100.00
07 ACT OUT RATED FULL LOAD
80.000
0.00
100.00
08 BASE LOAD MINIMUM (KW)
20.000
10.00
30000.00
09 BASE LOAD REFERENCE (KW)
50.000
0.00
30000.00
10 BASE LOAD MAXIMUM (KW)
110.000
10.00
30000.00
11 BASELOAD RAISE TIME(SEC)
60.000
1.00
600.00
12 BASELOAD LOWER TIME(SEC)
60.000
1.00
600.00
13 UNLOAD TRIP LEVEL (KW)
5.000
0.00
30000.00
14 LOADING RATE (KW/SEC)
20.000
1.00
600.00
15 UNLOADING RATE (KW/SEC)
20.000
1.00
600.00
16 ENABLE FAST LOAD RATE
FALSE
TRUE
FALSE
17 FAST RAMP ENABLE LOAD(%)
80.000
1.00
110.00
18 FAST RAMP RATE (KW/SEC)
60.000
1.00
600.00
O**ACTUATOR BUMP SETUP**
01 ACT BUMP ENABLE
FALSE
TRUE
FALSE
02 ACT BUMP LEVEL (%FD)
1.000
0.00
25.00
03 ACT BUMP DURATION (SEC)
0.110
0.08
2.00
04 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
P**ANALOG INPUTS SETTINGS**
01 AI 1 CONFIGURED FOR:
Monitor
02 AI 2 CONFIGURED FOR:
Monitor
03 SPEED w/ RMT IN@MIN(RPM)
800.000
0.00
4000.00
04 SPEED w/ RMT IN@MAX(RPM)
1000.000
0.00
4000.00
05 RMT SPEED REF INPUT(RPM)
Monitor
06 RMT SPDREF INC TIME(SEC)
30.000
1.00
300.00
07 RMT SPDREF DEC TIME(SEC)
30.000
1.00
300.00
08 BSLOAD w/RMT IN@MIN (KW)
20.000
0.00
30000.00
09 BSLOAD w/RMT IN@MAX (KW)
90.000
10.00
30000.00
10 RMT BSLOAD REF INPUT(KW)
Monitor
11 RMT BSLOAD INC TIME(SEC)
60.000
1.00
600.00
12 RMT BSLOAD DEC TIME(SEC)
60.000
1.00
600.00
13 REMOTE AUX SCALE(%/VOLT)
3.000
0.10
5.00
14 SYNC INPUT SCALE(%/VOLT)
0.700
0.10
5.00
15 MAP LIMITER IN MIN (EU)
0.000
-10000.0
10000.0
16 MAP LIMITER INPUT MAX (EU)
20.000
-10000.0
10000.0
17 EXT LOAD SENSOR MIN (EU)
0.0
-10000.0
10000.0
18 EXT LOAD SENSOR MAX (EU)
500.0
-30000.0
30000.0
19 EXT LOAD SNSR FILTER (S)
0.01
0.01
10.0
Q**DISCRETE OUT SETTINGS**
01 RELAY 1 SELECTED AS
Monitor
02 RELAY 1 LEVEL SW (1-6)
1
1
6
03 RELAY 1 LEVEL SELECT FOR
Monitor
04 RELAY 1 ON LEVEL =
0.000
-32000.00
32000.00
05 RELAY 1 OFF LEVEL =
0.000
-32000.00
32000.00
06 RELAY 2 SELECTED AS
Monitor
07 RELAY 2 LEVEL SW (1-6)
1
1
6
08 RELAY 2 LEVEL SELECT FOR
Monitor
09 RELAY 2 ON LEVEL =
0.000
-32000.00
32000.00
10 RELAY 2 OFF LEVEL=
0.000
-32000.00
32000.00
11 RELAY 3 SELECTED AS
Monitor
12 RELAY 3 LEVEL SW (1-6)
2
1
6
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...