2301E Digital Control
Manual 26641
108
Woodward
10 RELAY 2 OFF LEVEL=
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units.
(M
ust be less than the ‘Relay On Level’).
11 RELAY 3 SELECTED AS
(monitor)
Displays the function selected for terminal 43. This relay is selected in the
configure menu D**DISCRETE OUT OPTIONS**
12 RELAY 3 LEVEL SW (1-6)
dflt = 2 (1, 6)
Select one of the following parameters for discrete output at terminals 43 when it
was selected as a level switch.
1
NOT USED
2
ACTUAL SPEED
3
SPEED SETPOINT
4
START LIMITER SETPOINT
5
ACTUATOR DEMAND
6
GENERATOR OUT (LOAD SENSOR)
13 RELAY 3 LEVEL SELECT FOR
(monitor)
Displays the level function selected for terminal 43.
14 RELAY 3 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows you to program the desired
hysteresis for the function selected.
15 RELAY 3 OFF LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units (must be less than the
‘Relay On Level’).
16 RELAY 4 SELECTED AS
(monitor)
Displays the function selected for terminal 44. This relay is selected in the
configure menu
—D**DISCRETE OUT OPTIONS**
17 RELAY 4 LEVEL SW (1-6)
dflt = 1 (1, 6)
Select one of the following parameters for discrete output at terminals 44 when it
was selected as a level switch.
1
NOT USED
2
ACTUAL SPEED
3
SPEED SETPOINT
4
START LIMITER SETPOINT
5
ACTUATOR DEMAND
6
GENERATOR OUT (LOAD SENSOR)
18 RELAY 4 LEVEL SELECT FOR
(monitor)
Displays the level function selected for terminal 44
19 RELAY 4 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows the user to program the
desired hysteresis for the function selected.
20 RELAY 4 OFF LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’).
21 BREAKER OPEN TIME (SEC)
dflt = 1.000 (0.80, 500.00)
Sets the time the automatic circuit breaker command time is will change states
(depending on the configuration of CB Open Relay Normally Energized).
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...