will ramp to the Remote Reference input value at the remote reference increase
or decrease rate settings. This may not be the desired mode of operation, so be
sure to understand the implications of operating the control in this manner.
If a difference is detected between the present speed reference and the remote
reference rpm value, the present speed reference is ramped up or down at the
increase or decrease rate until the present speed reference matches the remote
speed reference rpm value. The remote reference will not increase/decrease the
speed reference above the maximum input value or below the minimum input
value. (See Figure 3-3.)
Figure 3-3. Remote Speed Reference