Manual 26641
2301E Digital Control
Woodward
9
Chapter 2.
Installation
Introduction
This chapter contains general installation instructions for the 2301E control.
Power requirements, environmental precautions, and location considerations are
included to determine the best location for the control. Additional information
includes unpacking instructions, electrical connections, and an installation check-
out procedure.
Due to typical noise levels in engine and turbine
environments,
hearing protection should be worn when working on or around the
2301E.
The surface of this product can become hot enough or cold enough
to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification
section of this manual.
External fire protection is not provided in the scope of this product. It is
the responsibility of the user to satisfy any applicable requirements for
their system.
Unpacking
Before handling the control, read all of this chapter and
“Electrostatic Discharge
Awareness” at the beginning of this manual. Be careful when unpacking the
electronic control. Check the control for signs of damage such as bent or dented
panels, scratches, and loose or broken parts. If any damage is found,
immediately notify the shipper. Do not take the control out of the ESD bag it ships
in until ESD precautions are in place. Keep yourself discharged while handing
the unit outside the ESD bag, at least until it is grounded.
Power Requirements
The 2301E control requires a voltage source of 18 to 36 Vdc, with a current
capacity of at least 600 mA for operating power. If a battery is used for operating
power, an alternator or other battery charging device is necessary to maintain a
stable supply voltage. The battery charging device should be suppressed from
load dump events or the power bus must have central suppression. The 2301E
does not have sufficient capability to withstand all battery load dump events.
To prevent damage to the control, make sure that the alternator or
other battery-charging device is turned off or disconnected before
disconnecting the battery from the control.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...