Manual 26641
2301E Digital Control
Woodward
45
Generator Breaker Open Pulse
The Generator Breaker Open Pulse feature must utilize the PT and CT signals
connected to the 2301E. These signals measure the actual kW Load coming into
the control. When the Load is greater than a preset value and the generator
breaker opens, the fuel demand will instantly go to zero fuel for an adjustable
period of time. This is proven to help keep the engine speed from overspeeding.