2301E Digital Control
Manual 26641
106
Woodward
08 BSLOAD W/RMT IN@MIN (KW)
dflt = 20.000 (0.00
–30000.00)
Sets the Base Load reference value when the remote reference input is at the
low value for the selected range. This value may be less than or greater than the
value entered when the input is at maximum.
09 BSLOAD W/RMT IN@MAX (KW)
dflt = 90.000 (10.00
–30000.00)
Sets the Base Load reference value when the remote reference input is at the
maximum value for the selected range.
10 RMT BSLOAD REF INPUT (KW)
(monitor)
Displays the baseload reference based on the analog input.
This displayed value is the result of the input parameter, it is not
limited by the ramp times or switch input logic.
11 RMT BSLOAD INC TIME(SEC)
dflt = 60.000 (1.00
–600.00)
Sets the time for the Base load reference, ramp from the 4 mA setting to the
20 mA setting.
12 RMT BSLOAD DEC TIME(SEC)
dflt = 60.000 (1.00
–600.00)
Sets the time for the Base load reference to ramp from the 20 mA setting to the
4 mA setting.
13 REMOTE AUX SCALE(%/VOLT)
dflt = 3.000 (0.10
–5.00)
Sets the gain of the remote input when used to bias speed from a remote control
device. The normal scale is 3.0% speed change per volt input. The analog input
range is ±2.5 V.
14 SYNC INPUT SCALE(%/VOLT)
dflt = 0.70 (0.10
–5.00)
Sets the gain of the synchronizer input when used to bias speed from a speed
and phase matching device. The normal scale is 0.7% speed change per volt
input. The analog input range is ±2.5 V.
15 MAP LIMITER INMIN (EU)
dflt = 0.0 (
–10000–10000)
Sets the manifold air pressure in Engineering Units value at 4 mA. This is the
setting for the value of the pressure sensor at 4 mA.
16 MAP LIMITER INMAX (EU)
dflt = 20.0 (
–10000–10000)
Sets the manifold air pressure in Engineering Units value at 20 mA. This is the
setting for the value of the pressure sensor at 20 mA.
17 EXT LOAD SENSOR MIN (EU)
dflt = 0.0 (
–10000–10000)
Sets the external load sensor value at the minimum value in engineering units
(watts, kilowatts, megawatts).
18 EXT LOAD SENSOR MAX (EU)
dflt = 500.0 (
–30000–30000)
Sets the external load sensor value at the maximum value in engineering units
(watts, kilowatts, megawatts).
19 EXT LOAD SNSR FILTER (S)
dflt = 0.01 (0.01
–10)
Adjusts the cutoff frequency of a low pass filter used on the external load sensor.
If the load sensor is electrically noisy, this will help attenuate the noise.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...