
Manual 26641
2301E Digital Control
Woodward
37
When in baseload operation, the baseload reference determines the load on the
generator without regard to other units connected to the same load. When the
generator is carrying less load than the base load reference, the load bias is
positive and the closed loop path increases the fuel to the engine. When the
generator is carrying more load than the base load reference, the load bias is
negative and the closed loop path will decrease the fuel to the engine. As the fuel
to the engine is changed, the load and/or speed will change until the engine
speed exactly matches the biased speed reference. At this steady state base
load condition, the load bias is virtually zero and the biased speed reference,
rated speed reference, and engine speed are virtually equal.
Opening the baseload input contact ramps the generator load from base load
back into isochronous load sharing. However, opening the load input contact
(unload) instead, ramps the generator load from the base load setting to the
unload trip level where a breaker trip signal is issued after a tunable time delay.
In isolated bus applications, a brief speed transient may occur when
the load sharing relay closes following transfer from baseload back
into isochronous load sharing.
It is possible for the control to be in base load control while supplying power to a
load which is isolated from the infinite bus. The capability of the engine generator
must be considered when operating this way. As an example consider two
generators, one capable of providing 1200 kW and one capable of providing 600
kW. If the combined load demand to these generators is 750 kW while the 1200
kW generator is in steady state isochronous load sharing and the 600 kW
generator is in steady state base load with a set point of 250 kW, the 1200 kW
generator will again be carrying 500 kW and the 600 kW generator will again be
carrying 250 kW. However, now as the total load demand increases only the
1200 kW generator will respond to the increase. At a combined load demand of
1450 kW, the 1200 kW generator will carry 1200 kW while the 600 kW generator
in base load will still be carrying 250 kW. If the load demand exceeds 1450 kW,
the steady state frequency of the bus will decrease and the load supplied by
each individual generator will increase.
Soft Loading
The load command discrete input contact controls soft loading. If the load
command discrete input is closed when the breaker (CB AUX) input contact
closes, the generator will soft load to the reference level of the mode selected
(load sharing or base load). If the load command discrete input is open (unload)
when the breaker (CB AUX) closes, the generator will immediately load to the
Unload Trip Level set in the KW Setting menu. When the load command discrete
input is closed, the generator will soft load to the reference level of the mode
selected (load sharing or base load). The ramp rate is adjustable. Soft Unloading
and Open Generator Breaker Relay Output
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...