14. Enter the calculated Reset, Compensation, and Gain setting into the control.
Save these settings in the control. The assumption is these settings will
produce good performance as shown in Figure 5-2. If this is not the case,
recheck all readings and calculations or repeat this entire procedure.
Figure 6-2. Trend Tool Trace Example 2
15. Bump the actuator (you can use a larger bump this time) to test control
response. Figure 5-2 shows the expected response.
Figure 6-3. Trend Tool Trace Example 3
16. Initiate load steps on and off to confirm acceptable and stable response.
Figure 5-3 shows the expected response. Note how the fuel demand
increases/decreases quickly with negligible overshoot.
17. This usually concludes the dynamic adjustment for one set of dynamics.
These settings are typically robust. Overly aggressive adjustments should be
avoided if possible. The Reset and Compensation settings produced by this
procedure are normally not changed. Increases to the Gain may produce
some improvement in the load transient response, however Window Width
and Gain Ratio (to be described in the next few steps) may be more
effective. It is also our experience that these settings are good for rated
speed as well as idle speed. Verify this for yourself by changing to rated
speed and performing some load transients. If you feel that the response can
be improved, we recommend leaving Reset and Compensation as they are
and only adjusting Gain.
18. Repeat this procedure for other dynamic adjustment sets as considered
necessary for alternate fuel supplies or operating conditions.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...