Manual 26641
2301E Digital Control
Woodward
113
06 LOAD PULSE DERIV %/S
dflt = -100.00 (-1000.00
–5000.00)
This value represents the level of change in generator load at which the Load
Pulse logic is activated for large load acceptances. When this level is reached,
the load step value used with the value “07 LS PULSE MULT ACT %/S” is added
to the actuator output.
07 LD PULSE MULT ACT %/S
dflt = 1.000 (
–100.00–100.00)
This represents the value that multiplies the measured load acceptance step and
add this to the actuator output in case of a large load acceptance. This step is
momentary and will return to zero. The rate at which this happens can be
modified in “08 LD PUL RECOVER RATE %/S”.
08 LD PUL RECOVER RATE %/S
dflt = 15.00 (0.00
–1000.00)
This value determines the rate (actuator %/S) at which the actuator pulse is
ramped back to zero.
09 BREAKER DELAY TIME
dflt = 2.00 (0.00
–10.00)
This value determines the time required for a delay after the breaker closes. This
prevents an immediate pulse during breaker closure
10 ENABLE FREQUENCY CONTROL
dflt = FALSE (TRUE, FALSE)
This parameter enables (TRUE) or disables (FALSE) the Frequency Control
feature. This feature will enable a small integrator which will allow the grid
frequency of an isolated or islanded system to be maintained within a very small
percentage over time.
11 ENABLE CB LOAD REJECTION
dflt = FALSE (TRUE, FALSE)
This parameter enables (TRUE) or disables (FALSE) the Generator Breaker
Rejection feature. This feature, when enabled, will lower the Fuel Demand to the
engine if the generator breaker opens and the generator load percentage is
above the
12- GEN REJ LOAD LEVEL
for the
13-GEN REJ PULSE TIME
.
12 GEN REJ LOAD LEVEL
dflt = 60.00 (0.00
–10.00)
This value determines the load percentage required for the CB LAOD
REJECTION to react. The load percentage must be above this value.
13 GEN REJ PULSE TIME
dflt = 0.20 (0.00
–2.00)
This value determines the pulse
X**ADAPTIVE FILTER SET**
01 ADAPTIVE FILTER ENABLE
dflt = TRUE (TRUE, FALSE)
Enables / Disables the Adaptive Filter used with Configure Menu B**ENG
—GEN
CNTRL FUNCTIONS, 02 SPEED SENSING TYPE, #5
—Adaptive Speed
Sensing.
02 ADAPTIVE FILTER GAIN
dflt = 0.25 (0.01
–1.00)
This value is typically left at the default value.
Y**APPLICATION INFO**
01 APP SOFTWARE NUMBER
(monitor)
Indicates the number of the software in the control.
02 APP SOFTWARE REVISION
(monitor)
Shows the revision of the software in the control.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...