Manual 26641
2301E Digital Control
Woodward
103
MAP LIMIT Y1
P
R
E
S
S
X
1
MANIFOLD AIR PRESSURE
0
100
MAP LIMITER FUNCTION
% FUEL
DEMAND
MAP LIMIT Y2
MAP LIMIT Y5
MAP LIMIT Y3
MAP LIMIT Y4
P
R
E
S
S
X
2
P
R
E
S
S
X
3
P
R
E
S
S
X
4
P
R
E
S
S
X
5
Figure 4-13. MAP Limiter Function
N**LOAD SETTINGS**
The Load Setting section is the set-up of the generator load control parameters.
01 KW LOAD DROOP %
dflt = 5.000 (0.00
–12.00)
This is the percentage of rated speed the speed reference will droop when the
generator load (KW) is increased to maximum load. Set to the desired droop
percent.
02 LOAD LEVEL VOLTAGE
dflt = 6.000 (0.10
–9.00)
Sets the voltage level of the load. The value of 6.0 is typical for most analog load
sharing schemes.
03 LOAD SHARE GAIN
dflt = 1.000 (0.01
–10.00)
Sets the load sharing gain. A too-high gain will result in unstable load sharing
between the units.
04 ENABLE ACT POS DROOP
dflt = FALSE (TRUE, FALSE)
This enables the actuator position droop feature. Actuator position droop is a
feature that gives the control a speed droop percentage based on the actuator
position (fuel demand). This feature would be used if the control was not capable
of receiving a PT and CT signal for KW droop, or if for testing purposes.
05 ACT POSITION DROOP %
dflt = 0.00 (0.00
–100.00)
The actuator dependant droop percentage setting, for proper droop control set
the below parameters 06 and 07 first. If load (kW) droop is used (GEN PT and
GEN CT are connected) set this parameter to 0.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...