2301E Digital Control
Manual 26641
94
Woodward
K**Dynamics #2 5 Pt Gain**
The Dynamics 2 control parameters are adjusted the same as Dynamics 1
described above. These parameters are in control only when the CB Aux contact
input is closed, or if a discrete input is configured for Select 2
nd
Dynamics and
this input is closed.
K**Dynamics #2 5 Pt Gain** parameters 04 thru 19 have the same
effect on speed control response as J
**
Dynamics #2 5 Pt Gain**
parameters 01 thru 16 described above.
01 ENABLE DYNAMICS 2 W/CB
dflt = FALSE (FALSE, TRUE)
When TRUE, the second set of dynamics is enabled when the circuit breaker
auxiliary contact or Select 2
nd
Dynamics contact is closed. When this prompt is
FALSE, only Dynamics 1 with be used to set speed control response.
02 DELAY DYN 2 ENABLE (SEC)
dflt = 0.00 (0.00
–20.00)
A delay time, in seconds, that dynamics #1 will continue to be used by the speed
control after the CB contact.
03 DELAY DYN 1 ENABLE (SEC)
dflt = 0.00 (0.00
–20.00)
The delay time that dynamics #2 will continue to be used before switching to
dynamics #1.
04 BREAKPOINT 2A (%LD OR RPM)
dflt = 99.60 (0.01
–5000.00)
05 GAIN @BREAKPOINT 2A
dflt = 2.0 (0.001
–100.00)
06 BREAKPOINT 2B (%LD OR RPM)
dflt = 99.70 (0.01
–5000.00)
07 GAIN @BREAKPOINT 2B
dflt = 2.0 (0.001
–100.00)
08 BREAKPOINT 2C (%LD OR RPM)
dflt = 99.80 (0.01
–5000.00)
09 GAIN @BREAKPOINT 2C
dflt = 2.0 (0.001
–100.00)
10 BREAKPOINT 2D (%LD OR RPM)
dflt = 99.90 (0.01
–5000.00)
11 GAIN BREAKPOINT 2D
dflt = 2.0 (0.001
–100.00)
12 BREAKPOINT 2E (%LD OR RPM)
dflt = 100.00 (0.01
–5000.00)
13 GAIN BREAKPOINT 2E
dflt = 2.0 (0.001
–100.00)
14 RESET 2
dflt = 1.00 (0.01
–100.00)
15 ACTUATOR COMPENSATION 2
dflt = 0.10 (0.01
–100.00)
16 WINDOW WIDTH 2 (RPM)
dflt = 60.00 (1.00
–200.00)
17 GAIN RATIO 2
dflt = 1.0 (1.00
–10.00)
18 SPEED FILTER FREQ 2 (HZ)
dflt = 12.00 (4.00
–20.00)
19 BUMP ACT TRIG (T THEN F)
dflt = FALSE (FALSE, TRUE)
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...