2301E Digital Control
Manual 26641
104
Woodward
06 ACT OUT AT RATED NO LOAD
dflt = 20.00 (0.00
–100.00)
The minimum setting where actuator position droop is calculated from. Adjust this
setting at the same reading of the Fuel Demand % when engine is running at
rated rpm but with no load.
07 ACT OUT RATED FULL LOAD
dflt = 80.00 (0.00
–100.00)
The maximum setting where actuator position droop is calculated from. Adjust
this setting at the same reading of the Fuel Demand % when engine is running at
rated rpm but with full load.
08 BASE LOAD MINIMUM (KW)
dflt = 20.000 (10.00
–30000.00)
The minimum value the base load reference will ramp to when the external lower
switch at terminal 39 is closed.
09 BASE LOAD REFERENCE (KW)
dflt = 50.000 (0.00
–30000.00)
Enter the internal Baseload set point. This sets the initial internal set point of the
Baseload Reference Ramp when the Load Control enters Base Load mode.
10 BASE LOAD MAXIMUM (KW)
dflt = 110.000 (10.00
–30000.00)
The maximum value the base load reference will ramp to when the external raise
switch at terminal 38 is closed.
11 BASELOAD RAISE TIME (SEC)
dflt = 60.000 (1.00
–600.00)
The time for the reference to ramp from baseload minimum to baseload load
maximum values entered above.
12 BASELOAD LOWER TIME (SEC)
dflt = 60.000 (1.00
–600.00)
The time for the reference to ramp from baseload maximum to baseload load
minimum values entered above.
13 UNLOAD TRIP LEVEL (KW)
dflt = 5.000 (0.00
–30000.00)
Enter the unload trip level set point. This sets the load level that the unit unloads
to following an Unload command. When the Load switch is opened to unload, the
generator unloads to this KW value. The Discrete output 4 will then change state
momentarily to give a breaker open command.
14 LOADING RATE (KW/SEC)
dflt = 20.000 (1.00
–600.00)
Enter the loading rate. This sets the rate at which the Load Ramp will increase
for soft loading.
15 UNLOADING RATE (KW/SEC)
dflt = 20.000 (1.00
–600.00)
Enter the unloading rate. This sets the rate at which the Load Ramp will
decrease for soft unloading.
16 ENABLE FAST LOAD RATE
dflt = FALSE (TRUE, FALSE)
Set to TRUE if the function to activate a faster loading ramp rate than the
LOADING RATE entered above when the system load level is high.
17 FAST RAMP ENABLE LOAD (%)
dflt = 80.000 (1.00
–110.00)
When the system load, as measured through the load sharing lines, is
determined to by above this percentage the soft load ramp rate will switch to a
faster rate to allow this oncoming unit to pick up it share of the load faster.
18 FAST RAMP RATE (KW/SEC)
dflt = 60.000 (1.00
–600.00)
Enter the loading rate at which the load will increase when the system load is
above the percentage entered above.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...