2301E Digital Control
Manual 26641
150
Woodward
SERVICE MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MIN.
MAX.
G**SPEED SETTINGS**
01 START SPEED (RPM)
400.000
1.00
2100.00
02 RAISE SPEED LIMIT (RPM)
1000.000
0.00
4000.00
03 LOWER SPEED LIMIT (RPM)
800.000
0.00
4000.00
04 IDLE SPEED (60 HZ) (RPM)
600.000
0.00
4000.00
05 IDLE SPEED (50 HZ) (RPM)
450.000
0.00
4000.00
06 ACCEL RAMP TIME (SEC)
20.000
1.00
300.00
07 DECEL RAMP TIME (SEC)
20.000
1.00
300.00
08 SPEED TRIM INC TIME(SEC)
30.000
1.00
300.00
09 SPEED TRIM DEC TIME(SEC)
30.000
1.00
300.00
10 IDLE DROOP BREAKPOINT
40.000
0.50
100.00
11 IDLE DROOP (%)
5.000
0.00
100.00
12 DELAY TIME IDLE TO RATED
5.000
0.00
600.00
H**DYNAMICS #1**
01 IDLE PROP GAIN 1
1.000
0.001
100.00
02 RATED PROP GAIN 1
2.000
0.001
100.00
03 RESET 1
1.000
0.01
100.00
04 ACTUATOR COMPENSATION 1
0.10
0.01
100.00
05 WINDOW WIDTH 1 (RPM)
60.000
1.00
200.00
06 GAIN RATIO 1
1.000
1.00
10.00
07 GAIN SLOPE
0.000
-50.00
50.00
08 GAIN BREAKPOINT
20.00
0.00
100.00
09 SPEED FILTER FREQ 1 (HZ)
12.000
4.00
20.00
10 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
11 PID DYNAMICS IN USE
Monitor
I**DYNAMICS #2**
01 ENABLE DYNAMICS 2 w/CB
FALSE
TRUE
FALSE
02 DELAY DYN 2 ENABLE (SEC)
0.00
0.00
20.00
03 DELAY DYN 1 ENABLE (SEC)
0.00
0.00
20.00
04 PROP GAIN 2
2.000
0.001
100.00
05 RESET 2
1.000
0.001
100.00
06 ACTUATOR COMPENSATION 2
0.10
0.01
100.00
07 WINDOW WIDTH 2 (RPM)
60.000
1.00
200.00
08 GAIN SLOPE 2
0.000
-50.00
50.00
09 GAIN BREAKPOINT 2
20.00
0.00
100.00
10 GAIN RATIO 2
1.000
1.00
10.00
11 SPEED FILTER FREQ 2 (HZ)
12.000
4.00
20.00
12 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
13 PID DYNAMICS IN USE
Monitor
J**DYNAMICS #1, 5 PT GAIN**
01 BREAKPOINT 1A (%LD or RPM)
99.600
0.01
5000.00
02 GAIN @BREAKPOINT 1A
4.0
0.01
100.00
03 BREAKPOINT 1B (%LD or RPM)
99.700
0.01
5000.00
04 GAIN @BREAKPOINT 1B
4.0
0.01
100.00
05 BREAKPOINT 1C (%LD or RPM)
99.800
0.01
5000.00
06 GAIN @BREAKPOINT 1C
4.0
0.01
100.00
07 BREAKPOINT 1D (%LD or RPM)
99.900
0.01
5000.00
08 GAIN @BREAKPOINT 1D
4.0
0.01
100.00
09 BREAKPOINT 1E (%LD or RPM)
100.00
0.01
5000.00
10 GAIN @BREAKPOINT 1E
4.0
0.01
100.00
11 RESET 1
2.000
0.01
100.00
12 ACT COMPENSATION
12.000
0.01
100.00
13 WINDOW WIDTH 1 (RPM)
60.000
1.00
200.00
14 GAIN RATIO 1
1.000
1.00
10.00
15 SPEED FILTER FREQ 1 (HZ)
12.000
4.00
20.00
16 BUMP ACT TRIG (T THEN F)
FALSE
TRUE
FALSE
17 PID DYNAMICS IN USE
Monitor
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...