Manual 26641
2301E Digital Control
Woodward
153
SERVICE MENU
PROGRAMMED
VALUE
DEFAULT
VALUE
TUNABLE RANGE
MIN.
MAX.
13 RELAY 3 LEVEL SELECT FOR
Monitor
14 RELAY 3 ON LEVEL =
0.000
-32000.00
32000.00
15 RELAY 3 OFF LEVEL =
0.000
-32000.00
32000.00
16 RELAY 4 SELECTED AS
Monitor
17 RELAY 4 LEVEL SW (1-6)
1
1
6
18 RELAY 4 LEVEL SELECT FOR
Monitor
19 RELAY 4 ON LEVEL =
0.000
-32000.00
32000.00
20 RELAY 4 OFF LEVEL =
0.000
-32000.00
32000.00
21 BREAKER OPEN TIME (SEC)
1.000
0.80
60.00
22 RAMP @ MIN,CB DELAY(SEC)
Monitor
23 INHIBIT MIN. CB DELAY
FALSE
FALSE
TRUE
R**ANALOG OUTPUT SETTINGS**
01 ANALOG OUTPUT SEL
1
1
10
02 ANALOG OUTPUT SELECTION
Monitor
03 4 mA OUTPUT VALUE
0.000
-200.00
200.00
04 20 mA OUTPUT VALUE
900.00
-200.00
32000.00
05 ANALOG OUT 1 (%)
Monitor
S**RELAY AND ANOUT TESTS**
01 ENABLE MANUAL DRIVR TEST
FALSE
TRUE
FALSE
02 FORCE OUTPUT STATUS
Monitor
03 TURN ON DO1
FALSE
TRUE
FALSE
04 DISCRETE OUTPUT #1
Monitor
05 TURN ON DO2
FALSE
TRUE
FALSE
06 DISCRETE OUTPUT #2
Monitor
07 TURN ON DO3
FALSE
TRUE
FALSE
08 DISCRETE OUTPUT #3
Monitor
09 TURN ON DO4
FALSE
TRUE
FALSE
10 DISCRETE OUTPUT #4
Monitor
11 TURN ON CB AUX RELAY
FALSE
TRUE
FALSE
12 LOAD SHARE RELAY
Monitor
13 ADJUST ANALOG OUTPUT (%)
0.000
0.00
100.00
14 ANALOG OUT (%)
Monitor
15 ADJUST ACTUATOR OUT (%)
0.000
0.00
100.00
16 ACTUATOR OUTPUT (mA)
Monitor
T**KW INPUT CALIBRATION**
01 ENTER RATED LOAD (KW)
500
10
30000
02 ENTER DERATED LOAD (KW)
400
10
30000
03 KW INPUT CALIBRATN ZERO
0.000
-20.00
20.00
04 KW INPUT CALIBRATN GAIN
13.000
5.00
40.00
05 GEN OUTPUT (READ KW)
Monitor
06 LOAD SIGNAL OUT (VDC)
Monitor
U**DISPLAY PID PARAMETERS**
01 DYNAMICS 2 ENABLED
Monitor
02 PID GAIN VALUE
Monitor
03 PID INTEGRAL GAIN VALUE
Monitor
04 PID ACT COMP VALUE
Monitor
05 PID DYNAMICS IN USE
Monitor
V**ANALOG IN/OUTPUT CALIB**
01 AnIN 1, Offset
0.000
-100.00
100.00
02 AnIN 1, Gain
1.000
0.00
10.00
03 AnIN 1, mA / Volt
Monitor
04 AnIN 2, Offset
0.000
-100.00
100.00
05 AnIN 2, Gain
1.000
0.00
10.00
06 AnIN 2, mA / Volt
Monitor
07 Actuator, Offset
0.000
-100.00
100.00
08 Actuator, Gain
1.000
-100.00
100.00
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...