2301E Digital Control
Manual 26641
168
Woodward
Appendix H.
Connecting a 2301E to Control a CAT
ADEM Control in the Direct Rack Mode
This appendix will step you through the process of using the 2301E to control a
CAT ADEM control in the Direct Rack Mode. This allows the 2301E to take
control of the engine speed for speed control, allows the user the ability to tune
the PID dynamic adjustments of the engine and use the PT/CT inputs for load
sharing, droop baseload and isochronous baseload operations.
1.0
Connect the ADEM control to Terminal 44 of the 2301E as shown:
2.0 In the 2301E Configuration Mode, select the Actuator Output Type to 4. This
activates Discrete Output #1 for a PWM output.
3.0 In the PWM Actuator Settings, select the settings as follows:
4.0 Verify that all of the speed settings and the number of flywheel teeth are set
properly. Be ready tune the dynamic adjustments if the engine is unstable.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...