Manual 26641
2301E Digital Control
Woodward
139
Modbus Function Codes
Code
Definition
Reference Address
01
Read Digital Outputs
0XXXX
(Raise/Lower and Enable/Disable Commands)
02
Read Digital Inputs
1XXXX
(Status Indications / Alarms and Trips)
03
Read Analog Outputs
4XXXX
04
Read Analog Inputs
3XXXX
(Speed, Setpt, etc.)
05
Write Single Discrete Output
0XXXX
(Raise/Lower and Enable/Disable Commands)
08
Loopback Diagnostic Test
N/A
(Subfunction 0 only)
15
Write Digital Outputs
0XXXX
16
Write Analog Outputs
4XXXX
Table 8-3. Modbus Function Codes
When a Modbus message is received, it is checked for any errors or invalid data.
If there is invalid data in the message, an error code is sent back to the master
and the control issues an alarm message. The error codes are defined in the
following table.
If the control has not received a message for the configured time-out period, the
control will give and alarm with an error message, but no message is sent to the
master. This time-out is defaulted to 5 seconds and only applies to units using
both monitor and control (adjustable in Service Mode).
Port Adjustments
Before the 2301E will communicate with the master device, the communication
parameters must be verified. These values are set in Service Mode.
Parameter
Port Adjustment Range
Baud Rate
9600 to 115200
Data Bits
7 or 8
Stop Bits
1, 2 or 1.5
Parity
NONE, ODD or EVEN
Table 8-4. Port Adjustments
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...