Manual 26641
2301E Digital Control
Woodward
107
Q**DISCRETE OUT SETTINGS *8
The 2301E has four discrete output driver channels. Terminals 41, 42, 43 and 44
are configurable and can be programmed to perform one of the following
functions.
And any of the four relays can also be programmed to function as a level switch.
When programmed as a level switch the relay will change state when the
selected parameter reaches the programmed level (energizes when value is
higher the programmed level).
01 RELAY 1 SELECTED AS
(monitor)
Displays the function selected for terminal 41. This relay is selected in the
Configure Menu D**DISCRETE OUT OPTIONS**.
02 RELAY 1 LEVEL SW (1-6)
dflt = 1 (1, 6)
Select one of the following parameters for discrete output at terminals 41 when it
was selected as a level switch.
1
NOT USED
2
ACTUAL SPEED
3
SPEED SETPOINT
4
START LIMITER SETPOINT
5
ACTUATOR DEMAND
6
GENERATOR OUT (LOAD SENSOR)
03 RELAY 1 LEVEL SELECT FOR
(monitor)
Displays the level function selected for terminal 41.
04 RELAY 1 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows you to program the desired
hysteresis for the function selected.
05 RELAY 1 OFF LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch OFF setting in engineering units (must be less than the
‘Relay On Level’).
06 RELAY 2 SELECTED AS
(monitor)
Displays the function selected for terminal 42. This relay is selected in the
configure menu D**DISCRETE OUT OPTIONS**.
07 RELAY 2 LEVEL SW (1-6)
dflt = 1 (1, 6)
Select one of the following parameters for discrete output at terminals 42 when it
was selected as a level switch.
1
NOT USED
2
ACTUAL SPEED
3
SPEED SETPOINT
4
START LIMITER SETPOINT
5
ACTUATOR DEMAND
6
GENERATOR OUT (LOAD SENSOR)
08 RELAY 2 LEVEL SELECT FOR
(monitor)
Displays the level function selected for terminal 42.
09 RELAY 2 ON LEVEL =
dflt = 0.000 (-32000.00, 32000.00)
Enter the level switch ON setting in engineering units. There is an ON and an
OFF setting for each level switch option. This allows you to program the desired
hysteresis for the function selected.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...