Manual 26641
2301E Digital Control
Woodward
15
The discrete inputs are capable through software programming to
change the logic or state of the input. Please verify the state of your
input before starting the engine.
Close to Run or Minimum Fuel (Terminal 34)
(Discrete Input A)
The external contact used to activate the Close to Run command connects to
terminal 34. This discrete input changes the control operation by immediately
decreasing the fuel demand to zero. When the switch or relay contacts are
closed, the control is allowed to control the fuel in an attempt to control the
speed/load of the prime mover. When the switch or relay contacts are open, the
Minimum Fuel Function will immediately pull the fuel demand to zero.
Do NOT use the minimum fuel contact as part of any emergency stop
sequence.
Discrete Inputs B, C, D (Terminals 35, 36, 37)
Discrete Inputs B, C and D (terminals 35, 36, and 37) are configurable for the
following functions:
Not used
Failed speed override
Reset
Select 2
nd
dynamics
Shutdown external
Idle/rated switch
Generator Breaker (52G) Isoch / Droop
Derate KW Load Reference
50/60 Hertz Operation
The Factory default settings are as follows:
Discrete input B (terminal 35) is configured for 2
– Reset.
Discrete input C (terminal 36) is configured for 6
– Idle/Rated switch.
Discrete input D (terminal 37) is configured for 7
– Generator Breaker
droop/Isochronous.
If none of functions are used, the Discrete Input should be set to Not Used.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...