Manual 26641
2301E Digital Control
Woodward
111
02 ENTER DERATED LOAD (KW)
dflt = 400.000 (10.00
–3000.0)
Adjust this value for the derated load of the generator.
03 KW INPUT CALIBRATN ZERO
dflt = 0.000 (-20.00
–20.00)
Adjust until the KW reading below is zero when the generator output is zero.
04 KW INPUT CALIBRATN GAIN
dflt = 13.000 (5.00
–40.00)
Adjusted to match the load sensor output to the external instrumentation
readings.
05 GEN OUTPUT (READ KW)
(monitor)
The output of the engine sensed load (should match external instrumentation).
06 LOAD SIGNAL OUT (Vdc)
(monitor)
Converts the generator KW into the Load Gain voltage value.
U**DISPLAY PID PARAMETERS**
This is a display of the input to the PID control. The values entered in the
Dynamic tuning section are normalized values and the values displayed here can
be used for stability analysis if needed.
01 DYNAMICS 2 ENABLED
(monitor)
Indicates the system is in the isochronous mode (CB aux is closed) and
Dynamics 2 values are being used to the input of the PID controller.
02 PID GAIN VALUE
(monitor)
This is the proportional value into the PID.
03 PID INTEGRAL GAIN VALUE
(monitor)
This is the Integral value into the PID, Reset rate.
04 PID ACT COMP VALUE
(monitor)
This is the derivative into the PID.
05 PID DYNAMICS IN USE
(monitor)
This value will indicate which set of dynamics are in use by the controller. The
choices that are shown here are:
PID USING DYNAMICS 1
PID USING DYNAMICS 2
PID USING 5-SLOPE - DYNAMICS 1
PID USING 5-SLOPE - DYNAMICS 2
V**ANALOG IN/OUTPUT CALIB**
01 AnIN 1, Offset
dflt = 0.000 (
–100.00–100.00)
Sets the offset of analog input 1.
02 AnIN 1, Gain
dflt = 1.000 (0.00
–10.00)
Sets the gain for analog input 1.
03 AnIN 1, mA / Volt
(monitor)
Shows the actual input value for input 1.
04 AnIN 2, Offset
dflt = 0.000 (
–100.00–100.00)
Sets the offset of analog input 2.
Содержание 2301E
Страница 14: ...2301E Digital Control Manual 26641 4 Woodward Figure 1 1a 2301E Outline Drawing Ordinary Locations...
Страница 15: ...Manual 26641 2301E Digital Control Woodward 5 Figure 1 1b 2301E Outline Drawing Hazardous Locations...
Страница 16: ...2301E Digital Control Manual 26641 6 Woodward Figure 1 2a 2301E Control Wiring Diagram sheet 1...
Страница 17: ...Manual 26641 2301E Digital Control Woodward 7 Figure 1 2b 2301E Control Wiring Diagram sheet 2...
Страница 18: ...2301E Digital Control Manual 26641 8 Woodward Figure 1 2c 2301E Control Wiring Diagram notes...
Страница 80: ...2301E Digital Control Manual 26641 70 Woodward This screen shows an example of the Final Settings...
Страница 100: ...2301E Digital Control Manual 26641 90 Woodward Figure 4 5 Typical Transient Response Curves...
Страница 181: ...Manual 26641 2301E Digital Control Woodward 171 Declarations...