Figure 7-60
Configuration of the D4x5‑2 I/Os (terminal X142)
Addresses tab
The start address for the X142 I/Os can be set in the "Addresses" tab. The address can be
specified or automatically assigned by the system.
Channel tab
The function of each individual I/O channel is set in the "Channel 0‑7" tab. Possible functions:
● DI
● DO
● Output cam
● Measuring input
All I/O channels can be inverted. A filter time of 1 μs or 125 μs can also be set for digital inputs
and measuring inputs.
The displayed logical address of a channel is only required when symbolic assignments are
not used.
7.12.1.3
Configuration of the CX32-2/CU3xx/TB30/TMxx I/O terminals
The configuration is performed in a similar way as for the onboard I/Os X122/X132 for the
SIMOTION D4x5‑2, i.e. the I/Os can be
● BICO-interconnected (use as drive I/O)
● Used by SIMOTION
Commissioning (software)
7.12 Configuring drive-related I/Os (with symbolic assignment)
SIMOTION D4x5-2
286
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B