3. All DRIVE-CLiQ connections (e.g. with the SINAMICS S120 Active Line Module) are also
detected automatically.
Note
As long as the RDY LED continues to flicker, power-up is not complete and it is not possible
to go online.
During commissioning the firmware of the components is upgraded or downgraded
automatically based on the firmware version on the CF card and the firmware version on
the SINAMICS components (DRIVE‑CLiQ components, TB30, CBE30-2, Power Modules,
etc.).
The update can take several minutes and its progress is tracked by corresponding
messages appearing in the alarm window of SIMOTION SCOUT.
SIMOTION D4x5‑2/CX32‑2/DRIVE‑CLiQ components:
A firmware update on DRIVE‑CLiQ components is indicated by the RDY LED flashing red
and green:
● FW update running: RDY LED flashes slowly (0.5 Hz)
● FW update complete: RDY LED flashes quickly (2 Hz), POWER ON required
These flashing patterns are also displayed by the yellow RDY LED on the SIMOTION D/
CX32‑2, and indicate that a firmware update is being performed on components connected
to the SIMOTION D/CX32‑2 or that all components have completed the firmware update.
Components requiring POWER ON following a firmware update signal this by means of the
fast flashing RDY LED. Go offline with SCOUT and switch the 24 V supply to the relevant
components off/on (POWER ON) to initialize.
CBE30-2 option board:
During the firmware update, the OPT LED of the SIMOTION D module and the SYNC LED
of the CBE30-2 flash green.
4. The first time it is switched on, the SIMOTION D4x5‑2 goes to STOP operating state
following power-up.
Following power-up, the SIMOTION D4x5‑2 is in a state in which it can be configured.
Commissioning (hardware)
5.1 Requirements for commissioning
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
99