Restoring the factory settings
1. Right-click "SINAMICS_Integrated" in the project navigator.
2. Select the "Target device > Restore factory settings" command from the context menu.
This restores the delivery state of SINAMICS Integrated.
Note
Use the same procedure for the CX32‑2 controller extension and the SINAMIC S120 drive
units.
7.18.5
Setting SIMOTION D4x5-2 to the factory settings
Overview
SIMOTION D4x5‑2 is supplied with preset parameters, such as the transmission rate or
PROFIBUS addresses. You can restore the default settings with the mode selector. This will
delete the following data:
● Non-volatile SIMOTION data in the SIMOTION device
● The backup copy of non-volatile SIMOTION data on the CF card (PMEMORY.XML/
PMEMORY.BAK)
● User data in the "volatile SIMOTION data" area and on the CF card
● The communication configuration (IP and DP parameters) on the CF card is set to the
factory settings.
The licenses on the CF card are retained.
Restoring default settings with the mode selector
1. The power supply is switched off.
2. Set the mode selector on the SIMOTION D4x5‑2 to MRES (switch position 3).
3. Switch on the power supply.
The NVRAM and the SIMOTION user data are deleted. The default settings are loaded.
SIMOTION D4x5‑2 remains in STOP mode.
4. Now use the mode selector to change to the desired operating state.
Note
The communication parameters are now reset to the default settings (PROFIBUS address
2, baud rate of 1.5 Mbit/s). The communication configuration for SIMOTION D4x5‑2 must
be performed again. The existing IP settings for the CBE30-2 are restored to the default
settings.
Commissioning (software)
7.18 Deleting data
SIMOTION D4x5-2
316
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B