LED
State
Comment
RDY
DP
Off
Red
FW checked
(no CRC error)
-
Red 0.5 Hz
Red 0.5 Hz
FW checked
(CRC error)
CRC invalid
Table 9-5
Firmware
LED
State
Comment
RDY
DP
Yellow
Not relevant
Initializing
–
Alternating
Running
See the table below
Table 9-6
CX32-2 – Description of the LEDs after ramp-up
LED
Color
State
Description, cause
Remedy
RDY
(READY)
-
Off
Electronic power supply is missing or outside the
permissible tolerance range.
Check power supply
Green
Continuous
light
The component is ready for operation and cyclic
DRIVE‑CLiQ communication is taking place.
–
Flashing
0.5 Hz
Commissioning/reset
–
Flashing
2 Hz
Writing to the memory card
–
Red
Flashing
2 Hz
General errors
Check parameterization/con‐
figuration data
Red/
green
Flashing
0.5 Hz
CX32‑2 is ready for operation.
However, software licenses are missing.
Obtain licenses
Yellow
Flashing
0.5 Hz
Firmware update of the connected DRIVE-CLiQ
components running
–
Flashing
2 Hz
DRIVE-CLiQ component firmware update com‐
plete. Wait for POWER ON for the components in
question.
Perform POWER ON for the
respective component
Green/
yellow
or
red/yel‐
low
Flashing
2 Hz
Component detection via LED is activated
(p0124[0]).
Note:
Both options depend on the LED state when com‐
ponent detection is activated via p0124[0] = 1.
–
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
394
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B