Application example
The system consists of a synchronous master (DP master) and at least one SIMOTION D4x5‑2
synchronous slave (DP slave). The synchronous master contains the master axis; the
synchronous slave contains the following axes:
● The axes in the SINAMICS Integrated of the D4x5‑2 synchronous slave must exhibit high
performance with a servo cycle clock of 1 ms and an internal DP cycle of 1 ms. This requires
that the internal fast PROFIBUS DP be decoupled from the slower external PROFIBUS DP.
● The PROFIBUS DP has, for example, a cycle time of 4 ms due to the quantity framework
on the bus; in all cases, its cycle time exceeds that of the cycle clock of the internal DP
interface.
● The master values are transmitted via the DP bus. Further nodes can also be connected
to the DP bus, e.g. DP drives, distributed I/Os, etc.
6ODYHLQWHUIDFH;
([WHUQDO'3
GULYHRSWLRQDO
([WHUQDO'3
GULYH
'3 PV
0DVWHULQWHUIDFH
6\QFKURQRXVPDVWHU
HJ3
'3F\FOH PV
6HUYR PV
6,027,21'[
,QWHUQDO'3 PV
6HUYR PV
,QWHUQDOGULYH
0DVWHU LQWHUIDFH ;
'3EXVPDVWHUYDOXHEXV'3F\FOHFORFN PV
'3F\FOHFORFN
,QWHUQDO'3
6\QFKURQRXVVODYH
Figure 6-5
Example of a cycle clock scaling for PROFIBUS DP
6.3.6
Internal PROFIBUS interface with DP Integrated < 0.5 ms
Requirement
The minimum settable cycle clock for the internal PROFIBUS interface (DP Integrated) is 0.5
ms.
Parameter assignment / addressing
6.3 Configuring PROFIBUS DP
SIMOTION D4x5-2
138
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B