See also Section Configuration of the D4x5-2 I/Os (terminal X122/X132) (Page 284)
Note
If symbolic assignment is activated retrospectively for a project in which message frames have
already been configured and interconnected, these can be changed together with the BICO
interconnections.
For this reason, make a backup copy of your project before activating the symbolic assignment.
TB30, TM15 DI/DO and TM31 are especially affected.
See also Section Symbolic assignment / adaptation (Page 169)
7.12.1.4
Configuration of the ET 200SP/MP timer DIDQ
The I/O terminals of the ET 200SP and ET 200MP timer DIDQ can be used as drive-related I/
Os for measuring input and output cam applications.
The DI/DQ timers are configured via the hardware configuration of STEP 7 or TIA Portal. The
properties of the I/O channel can be configured in the parameterization dialog box, for example
● Timer DI for use of the I/O as measuring input input or
● Timer DQ for use of the I/O as cam output
Note
For the technological use of the timer DIDQ, you must operate the I/O station isochronously
on PROFINET:
● ET 200SP timer DIDQ: With SCOUT or SCOUT TIA, IM 155-6 PN HF required
● ET 200MP timer DIDQ: Only with SCOUT TIA, IM 155-5 PN ST or HF required
Operation via PROFIBUS is not possible.
For detailed information on the configuration, see
Technology Modules TM Timer DIDQ for
SIMOTION SCOUT and SIMOTION SCOUT TIA Commissioning Manual
Commissioning (software)
7.12 Configuring drive-related I/Os (with symbolic assignment)
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
287