The FB _LineModule_control function block is available on the controller for control and
diagnostics of the infeed.
Note
Always create the infeed first so that the infeed "Closed-loop control operation" signal is
automatically interconnected to a drive when this is inserted.
Recommendation: If the drive unit has not been configured, use "Configure drive unit" in the
project navigator. "Configure drive unit" has the advantage that all basic settings for the drive
unit are queried via one wizard.
FB _LineModule_control
The _LineModule_control function block (FB) can be used to switch the infeed on and off and
also perform simple diagnostics.
The following infeeds are supported by the _LineModule_control function block:
● Basic Line Modules (BLM)
● Smart Line Modules (SLM)
● Active Line Modules (ALM)
The _LineModule_control FB is part of the command library of the "SIMOTION SCOUT"
engineering system. You can find the FB at "Drives" > "SINAMICS".
For detailed information on the _LineModule_control FB, refer to the SIMOTION SCOUT online
help or the
Standard Function for SINAMICS S120 Line Modules Function Manual.
CX32‑2
Further information on how to use line modules with the CX32‑2 can be found in Section
Interconnecting the infeed "Operation" signal on the CX32-2 (Page 221).
Additional references
For a detailed description of the control words and status words of the PROFIdrive message
frames for SINAMICS S120 drives, see the
SINAMICS S120 Commissioning Manual.
7.8.3
Using one infeed for several CUs
If the infeed is controlled from another control unit, then the Ready for operation signal of the
infeed (parameter r0863.0) must be connected to parameter p0864 "Infeed operation" of the
drive via a digital input/output. If this is not taken into account, the infeed may be damaged.
Commissioning (software)
7.8 Activating the infeed (line module)
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B