The following interconnections are available by default:
● On the SINAMICS Integrated, the "infeed ready" signal of all connected infeeds is provided
on the CU‑Link. This means the "infeed ready" signal is on all Controller Extensions CX32‑2
– can be picked off via r8510.0 for the first infeed
– via r8510.1 for the second infeed etc.
The default interconnections are only created if an infeed has be configured with a DRIVE-
CLiQ connection (CX32‑2 must first have been configured).
● The status of the onboard I/Os of the D4x5‑2 is forwarded to all CX32‑2, where it can be
picked off via r8511.0‑21.
● The status of the onboard I/Os of the CX32‑2 is forwarded to the relevant DO CU_LINK.
Default interconnections can be deleted by appropriate user configurations (e.g. by
configuration of the interconnection, see the previous item
①
). If an existing interconnection
is disconnected, an information dialog box will be displayed to indicate this.
Figure 7-38
Information dialog box when an existing interconnection is disconnected
The interconnection options via CU‑Link are explained below using an example.
Configuring example:
Task definition (example)
The ready signal of an infeed r0863.0 on CX32‑2 (X102) is to be interconnected to three other
CX32‑2 Controller Extensions and to the drives of the SINAMICS Integrated via CU‑Link. The
items indicated the necessary interconnection measures, which are explained in detail below.
Commissioning (software)
7.5 Additional information on configuring the SINAMICS Integrated
SIMOTION D4x5-2
246
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B