9.2.4.2
Restoring data with switch position "1" or "A"
Procedure
To restore the non-volatile SIMOTION data, proceed as follows:
Step
Switch position "1"
Switch position "A" (as of V4.4)
1.
Insert the CF card into the new SIMOTION D4x5‑2. The SIMOTION D4x5‑2 must be switched off!
2.
Set the service selector switch to "1."
The position of the mode switch is not relevant, i.e. the
set operating mode remains unchanged.
Service selector switch (position 1)
Set the service selector switch to "A."
The position of the mode switch is not relevant, i.e. the
set operating mode remains unchanged.
Service selector switch (position A)
3.
Switch the SIMOTION D4x5‑2 on.
Switch the SIMOTION D4x5‑2 on.
The flickering green SF LED indicates that restoration
is requested via position "A."
4.
Restoration is started automatically.
Turn the service selector switch to "1" to start restoration.
5.
Once restoration has been completed, the module will start up automatically.
6.
Switch the module off and turn the service selector switch back to "0."
7.
Switch the SIMOTION D4x5‑2 on again.
9.2.5
Back up diagnostic data and non-volatile SIMOTION data via the web server
SIMOTION devices provide a web server with already prepared standard web pages. These
pages can be displayed via Ethernet using a commercially available browser. Additionally, you
have the option of creating your own HTML pages and incorporating service and diagnostic
information.
Diagnostic data and non-volatile SIMOTION data can be backed up via the web server. The
home page of the web server is opened by entering the IP address of the SIMOTION device
in the address line of the browser; e.g. http://169.254.11.22
This opens the home page of the web server. To back up diagnostic data and non-volatile
SIMOTION data, call the "Diagnostic files" page from the "Diagnostics" menu.
Diagnostics
9.2 Diagnostic data and non-volatile SIMOTION data
SIMOTION D4x5-2
406
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B