Bias
Output
frequency
Bias is added to frequency
reference and reset to 0
Up 2 command
Frequency
reference
5 s
5 s
Figure 5.35 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
• Up/Down 2 with Frequency Reference from Other Input Sources
When the frequency reference is set by an another source than the digital operator, the bias value will be saved in
parameter d4-06 exactly 5 s after the Up/Down 2 command has been released. When the Run command is turned off or
the power is switched off, the drive will use the value saved in d4-06 when it restarts.
Bias
Output
frequency
Up 2 command
d4-06 value
5 s
Bias is saved in parameter d4-06
5 s
Figure 5.36 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note:
Make sure to set the Up/Down 2 limits properly when using d4-01 = 1 in combination with the Up/Down 2 function.
Refer to d4-08:
Frequency Reference Bias Upper Limit (Up/Down 2) on page 141
and
Refer to d4-09: Frequency Reference Bias Lower Limit (Up/
Down 2) on page 141
for details on the limit settings.
Clearing the Value that was Saved
Depending on which function is used, the frequency reference value that was saved can be cleared by:
• Releasing the acceleration hold input.
• Setting an Up or Down command while no Run command is active.
5.4 d: Reference Settings
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
139
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...