Status
Description
Open
Output frequency does not match the frequency reference while the drive is running
Closed
Output frequency is within the range of frequency reference ± L4-04
Note:
The detection works in both forward and reverse.
L4-04
L4-04
Frequency
reference
Output
frequency
Speed Agree 2
ON
OFF
Figure 5.59 Speed Agree 2 Time Chart
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 197
for details on setting the
detection width.
Setting 14: User Set Speed Agree 2 (f
ref
/f
set
Agree 2)
Closes whenever the actual output frequency and the frequency reference are within the Speed Agree Width (L4-04) of
the programmed Speed Agree Level (L4-03). As the detection level L4-03 is a signed value, detection works in the specified
direction only.
Status
Description
Open
Output frequency or frequency reference are outside the range of L4-03 ± L4-04
Closed
Output frequency and the frequency reference are both with in the range of L4-03 ± L4-04
+/- L4-04
L4-03
Output
frequency
User Set
Speed Agree 2
OFF
ON
Frequency
reference
Frequency
reference
Output
frequency
Figure 5.60 User Set Speed Agree 2 Example with Positive L3-04 Value
Refer to L4-03/04: Speed Agreement Detection Level and Detection Width (+/-) on page 197
for details on setting the
detection width.
Setting 15: Frequency Detection 3
Output is closed as long as the output frequency is below the detection level set in L4-03 plus the hysteresis set in L4-04.
It closes when the output frequency falls below L4-03. As the detection level L4-03 is a signed value, the detection works
in the specified direction only.
Status
Description
Open
Output frequency exceeded L4-03 plus L4-04.
Closed
Output frequency is below L4-03 or has not exceeded L4-03 plus L4-04 yet.
5.7 H: Terminal Functions
174
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...